background image

5

17

CommIssIonIng

HandIng over

The householder should receive:
•  A clear and concise demonstration of the boiler      
 

operation and any system controls.

•  This manual, the burner manufacturer’s manual
 

and any other instructions.

•  OFTEC forms CD10 and CD11.
•  The boiler passport.

The householder should be advised to:
•  Service the boiler annually and to ensure that the  
 

service records in the boiler passport are completed.

•  Read the terms and conditions of warranty.
•  Keep all boiler documentation in a safe place.

a commissioning record should be completed

and a copy retained by the engineer.

this can be found in the Boiler Passport.

annual servicing must be carried out by an ofteC 
registered  or  a  competent,  qualified  engineer,      
familiar with firebird products.

Do not commence service until both the electrical and oil 
supply to the boiler have been safely isolated.

tHe oIl tanK

Check for oil leaks. Draw off any accumulated water       and 
sludge from the tank by opening the drain valve. Turn 
off the oil supply and remove the filter bowl, then wash 
the element clean with Kerosene. Fit a new element if 
required.

tHe BoIler

Remove combustion access door for access to baffles and 
to clean heat exchanger.

Cleaning a firebird condensing boiler:

1.  Remove all baffles, including the tubular baffles in the 

condensing section and clean them.

2.  Remove the condensate trap and clean it, place a tray 

under the connection for the trap. Vacuum out any 
loose debris from the chamber.

3.  Clean the inside of the boiler with a vacuum cleaner.

4.  Refit all the baffles and the condensate trap securely.

5.  System pressure should not exceed 2 bar at full 

operating temperature. The expansion vessel should 
be checked during the annual service to ensure that it 
is operating correctly.

Check insulation sealing and the silver foil lining in 
combustion access door - replace if necessary. Check 
graphite seal and replace if necessary.  When refitting this 
door be careful not to damage the foil and insulation by 
over tightening.

Check that the condensate trap is secure in position, clean 
and free of combustion debris. ensure that the condensate 
drain is free and not blocked.

expansion vessel pre -charge pressure should be checked 
annually and set according to the system design.

tHe Burner

ensure correct specification replacement nozzle is 
used.

See page 30 for more information on the burner.

1.  Check all oil filters and replace as necessary.

2.  Remove burner, clean blast tube and ensure that 

airways are clear.

3.  ensure electrodes are clean, dry, not broken and are set 

as per burner specifications.

4.  Clean fan and photocell.

5.  once  again  check  flexible  oil  lines  and                      

connections  for  damage  or  leaks,  replace  as       
necessary. replace flexible oil lines every 2 years.

Combustion Check
1.  Carry out a combustion analysis.
2.  Follow the steps as set out in the burner set-up         

section.

3.  Check safety operation, pull out the photo cell, cover 

and make sure the burner locks out.

4.  Check the thermostat operation. 
5.  allow the boiler to operate for at least two full “on/off” 

cycles.

ensure service is recorded in boiler passport.

6

servICIng

Summary of Contents for silver Boilerhouse 15-20kW

Page 1: ...g Boilers Technical Manual HEATING SOLUTIONS This manual must remain with the householder once installation is complete Working towards a greener planet Silverpac Slimline Silverpac Silver Boilerhouse...

Page 2: ......

Page 3: ...rpac 22 8 2 Slimline Silverpac 23 8 3 Silver Boilerhouse 24 8 4 Silver Utility 25 9 Wiring 9 1 Silverpac 26 9 2 Slimline Silverpac 27 9 3 Silver Boilerhouse 28 9 4 Silver Utility 29 10 Burner 30 11 Te...

Page 4: ...let First Aid medical attention should be sought following eye contact or prolonged reddening of the skin The small quantities of adhesives and sealants used in the product are cured They present no k...

Page 5: ...status lights not included in Silver Boilerhouse and Silverpac models Set at Max 80 C Set at Mid 70 C Set at Min 60 C Burner Lockout The boiler is factory fitted with a burner control box lockout safe...

Page 6: ...12 A1 2014 BS EN 12831 2003 and the statutory requirements of the Building Regulations To ensure the highest standards of installation safety it is important that the boiler be installed in compliance...

Page 7: ...g manuals and BS 7074 Part 1 EN 12828 2003 etc Please note following important points before commencing installation Installation Commissioning Boilers must be installed commissioned and serviced by a...

Page 8: ...r the cleaning door This should be checked at regular intervals and cleaned during annual service The condensate line should be plastic and have a minimum diameter of 22mm dia have a fall from the boi...

Page 9: ...re connecting the condensate pump Condensate PUMP kit is available as an optional extra Boiler Sealed Condensate Drain Condensate Drain Trap Lime Stone Chippings Free Draining Soil Soak Away 500mm Fig...

Page 10: ...Cone Float Screw cap Seal Seal 1 Push screw cap into connector and screw onto socket 2 Place cone into frame and float into cone 3 Screw frame with cone and float into connector 5 Final assembly 4 Pus...

Page 11: ...Q Q R Pressure Jet Location Appliance Burner Type Condensing UK ROI NI A Directly below an opening airbrick opening window etc 1000mm 600mm B Horizontally to an opening airbrick opening window etc 100...

Page 12: ...to BS EN 303 1 5 Terminating positions must be at least 1 8m distant from an oil storage tank unless a wall with at least 30 minutes fire resistance and extending 300mm higher and wider than the oil s...

Page 13: ...ired to ventilate and to avoid overheating in the boiler area OPEN FLUE BOILER IN ROOM BOILER COMPARTMENT VENTILATED FROM OUTSIDE BOILER COMPARTMENT VENTILATED FROM ADJOINING ROOM 55mm2 kW 55mm2 kW 55...

Page 14: ...Balanced flue TOP mark Snorkel 1 Push the flap valve into the balanced flue air intake 2 Ensure that the flap valve is in the correct position 3 Push the snorkel hose over the flap valve and air inta...

Page 15: ...LVERPAC SLIMLINE SILVERPAC FLUE Put the 90 flue terminal with the cone on the boiler Fix the guard plate to the boiler and then the guard to the boiler Heatpac boiler after installation Fig 1 Fig 2 Fi...

Page 16: ...ate System 35 flexible liner suitable for condensing applications System 35 adaptor 500mm Adjustable length Boiler adaptor Condensing boiler Condensing boiler NOTE All brick chimney constructions must...

Page 17: ...oil tight Soldered joints are not permissible Before connecting to the boiler always flush the complete oil supply line and ensure that oil supply is completely clean and free of any dirt or foreign m...

Page 18: ...erly commissioned when first used u The boiler should be commissioned by an OFTEC registered or competent qualified engineer familiar with Firebird products u The installation certificate and the comm...

Page 19: ...the chamber 3 Clean the inside of the boiler with a vacuum cleaner 4 Refit all the baffles and the condensate trap securely 5 System pressure should not exceed 2 bar at full operating temperature The...

Page 20: ...S 7074 Part 1 BS 5449 OFTEC standards and all other relevant legislation Preset Pressure Relief Valve 2 bar Water Side Resistance 15 20kW 20 26kW 26 35kW Flow Rate To Give A Nominal Output At 10K Diff...

Page 21: ...d all other relevant legislation Preset Pressure Relief Valve 2 bar Water Side Resistance Flow Rate To Give A Nominal Output At 10K Differential Flow Rate Measured 2135 kg h Waterside Resistance 0 18...

Page 22: ...ive A Nominal Output At 10K Differential Flow Rate Measured 1642 kg h 2135 kg h 2874 kg h Waterside Resistance 0 18 mbar 0 18 mbar 0 18 mbar Flow Rate To Give A Nominal Output At 20K Differential Flow...

Page 23: ...W Flow Rate To Give A Nominal Output At 10K Differential Flow Rate Measured 1642 kg h 2135 kg h 2874 kg h Waterside Resistance 0 18 mbar 0 18 mbar 0 18 mbar Flow Rate To Give A Nominal Output At 20K D...

Page 24: ...1 Condensate hose 111537 111537 111537 9 1 Drain cock 111329 111329 111329 10 1 Heat deflector 210904 210904 210904 11 1 Flap valve adapter 114262 114262 114262 12 1 Flap valve 114192 114192 114192 13...

Page 25: ...ket 111317 7 1 Condensate trap 112184 8 1 Condensate hose 111537 9 1 Drain cock 111329 10 1 Heat deflector 210904 11 1 Flap valve adapter 114262 12 1 Flap valve 114192 13 1 Flue kit 411482 14 1 Contro...

Page 26: ...Flue gasket 112104 112104 112104 6 1 Stat pocket 111317 111317 111317 7 1 Condensate trap 112184 112184 112184 8 1 Condensate hose 111537 111537 111537 9 1 Drain cock 111329 111329 111329 10 1 Heat de...

Page 27: ...317 111317 7 1 Condensate trap 112184 112184 112184 8 1 Condensate hose 111537 111537 111537 9 1 Drain cock 111329 111329 111329 10 1 Heat deflector 210904 210904 210904 11 1 Air hose 111902 111902 11...

Page 28: ...hermostat Reset pin inside Screw off cover Temperture control dial Max 80 C Min 60 C IMIT dual thermostat Pump live Earth Neutral Permanent live Timed Switch live Neutral Earth Pump over run thermosta...

Page 29: ...e provided for with terminal connections in the control panel Use heat resistant cable Protect supply with 5A fuse Power to burner High temperture limit thermostat Reset pin inside Screw off cover Tem...

Page 30: ...ids and covers are properly replaced and secured correctly 4 A permanent power supply not timed should be available at boiler location This can be used for a frost thermostat and or an over heat therm...

Page 31: ...h temperture limit thermostat Reset pin inside Screw off cover Temperture control dial Max 80 C Min 60 C IMIT dual thermostat L1 switch live Pump over run thermostat 87 C L2 remote lockout lamp Please...

Page 32: ...Danfoss S H nozzles are a Diesel nozzle and have a tolerance of 15 when used with Kerosene KEROSENE SETTINGS FOR FIREBIRD BOILER RANGE USING RDB 2 2 BURNERS Variations in nozzle throughput flue type...

Page 33: ...accordance with a instruction technical manuals b all relevant standards and codes of practice 4 An OFTEC registered or competent qualified engineer using the correct installation and test equipment...

Page 34: ...ergy Consumption Sound Power Level kW GJ dB SILVERPAC 15 20kW A 20 92 50 N A 20 26kW A 26 92 72 N A 26 35kW A 35 92 95 N A SLIMLINE SILVERPAC 20 26kW A 26 92 72 N A SILVER BOILERHOUSE 15 20kW A 20 92...

Page 35: ......

Page 36: ...contact Firebird Heating Solutions Ltd dar s Industrial Estate Baile Mhic re Co Cork P12 HK51 Ireland t 353 0 26 45253 f 353 0 26 45309 e info firebird ie web www firebird ie Firebird Heating Solution...

Reviews: