Fire Sentry FS24X QuadBand Triple IR Installation Manual And Operating Manual Download Page 7

 

Model FS24X

 

Fire and Flame Detectors

 

INSTALLATION  GUIDE  and  OPERATING  MANUAL

 

 

 
 

Fire Sentry Corporation  

Document No. 6178-001 - Rev. Q 

© Copyright 2011 

All Rights Reserved 

Page 4 

1.3 

Features and Benefits 

 

Selectable Sensitivity (four settings) 

User can set an FSX Detector to four (4) different Detector sensitivity levels 

(see Section 3.2). 

 

Selectable Relay Options 

User configurable for a variety of dry contact relay interface options (see Section 3.2). 

 

Selectable 4 

– 20 mA Output 

User can set for Source or Sink non-isolated output (see Section 3.2). 

 

Selectable Communications 

User can configure for analog or digital communication outputs such as ModBus (see Section 3.2). 

 

Selectable Digital Communication Address 

Users can select unique 7-bit code (128 addresses) (see Section 3.2). 

 

Lower Power Consumption 

Requires smaller external power supplies and fewer system backup batteries. 

 

Dual Microprocessors 

Reduces the number of discrete Detector components, provides larger programming and memory 
capacity, and provides redundant self-checking. 

 

100% Solid-State Quantum IR Sensors 

Superior performance, stability, reliability, durability, and ruggedness. Provides higher MTBF and much 
wider operating temperature range. 

 

Higher Operating Temperature 

185°F (85°C) for more applications and 230°F (110°C) available for higher temperature applications. 

 

Lower Operating Temperature 

-40°F (-40°C) for more applications and -76°F (-60°C) available for lower temperature applications. 

 

Built-

In Automatic “Through-the-Lens” Self-Test 

Monitors window lens obscuration and checks the operation of the Detector’s Sensor Array and Electro-
Optical Electronics Module. 

 

Anodized Field Removable Detector Aluminum Module (Puck) 

Rugged, superior protection against EMI/RFI and handling plus easier field installation and replacement. 

 

Three Separate Bright LED’s (Red, Yellow, Blue) 

Field stat

us indicators with individual LED’s for Alarm, Fault and Normal conditions.  Provides superior 

Detector status viewing in bright outdoor environments (see Section 3.6). 

 

FSC Windows® based PC Interface 

User can perform remote FSX Detector diagnostics, real-time status, Real-Time Graphing (RTG

), 

SnapShot

 

data recording, and downloading FirePic’s

 

with Fire Sentry’s exclusive FSIM-2 USB 

Interface Unit and easy to use Windows

®

 based PC Software. 

 

Designed to Detect both Hydrocarbon and Non-Hydrocarbon Fires with one FSX

 Detector 

All fire and flame threats are sensed, not just hydrocarbon fires as with other Triple IR Flame Detectors. 

 

Designed, Manufactured, Tested, and Patented by Fire Sentry Corporation 

Over 28 years of proven fire / flame detection product excellence worldwide. 

1.4 

Applications 

Partial List of Applications:  

Refineries 

Gas Processing Plants 

Offshore Drilling and Production Platforms 

Cogeneration Plants 

Gas Collection Facilities 

Petroleum Product Pipelines & Pumping Stations 

Petrochemical Plants 

Gas Turbine Enclosures 

Commercial and Military Aircraft Hangars 

Hydrogen Storage 

LPG Storage/Distribution 

Rail and Truck Loading/Unloading Terminals 

Hydrogen Plants 

LNG Storage/Distribution 

Crude & Product Tank Farms 

Engine Test Cells 

General Warehouses 

Gasoline Loading Terminals 

Power Plants 

Aerosol Filling Facilities 

Product Storage Terminals 

Marine Terminals 

Paint and Solvent Storage 

Cold Storage Warehouses 

Airport Terminals 

Marine Engine Rooms 

Gas Compressor Buildings 

Summary of Contents for FS24X QuadBand Triple IR

Page 1: ...erved Fire Sentry Corporation FSC 23311 La Palma Avenue Tel 714 671 1100 Yorba Linda California 92887 Telephone 714 694 2700 Fax 714 694 2701 www firesentry com FS24X QuadBand Triple IRTM Multi Spectr...

Page 2: ...ns such as FS2 FS2X FS2X FS3 FS3X FS3X FS4 FS4X FS4X FS5 FS5X FS5X FS6 FS6X FS6X FS7 FS7X FS7X FS8 FS8X FS8X FS9 FS9X FS9X FS10X FS10X FS11 FS11X FS11X FS12 FS12X FS12X FS14 FS14X FS14X FS15 FS15X FS1...

Page 3: ...uctions 5 U2 2 Opening the Detector 6 U2 3 Detector Connections 7 U2 4 Installation Practices 8 U2 5 Start Up and Commissioning 10 USECTION 3 OPERATION 12U U3 1 Principle of Operation 12 U3 2 Configur...

Page 4: ...inum or 316 Stainless Steel enclosure The FS24X Detector electro optical electronics module puck is enclosed in a field replaceable black hard anodized aluminum puck that provides superior ruggedness...

Page 5: ...nduit Entries Two 2 in NPT or Two 2 25 mm Weight Aluminum 3 lbs 11 oz 1 7 kg approximately Stainless Steel 7 lbs 7 oz 3 4 kg approximately Enclosure Rating IP66 NEMA 4 NEMA 4X Vibration Meets or excee...

Page 6: ...Spectral Sensitivity 0 4 to 7 0 micron wavelengths QuadBand Triple IR Plus 1 2 5 Hazardous Area Calssifications See Section 4 7 3 on Page 23 Class I Division 1 Groups A B C D Class II Division 1 Group...

Page 7: ...tor s Sensor Array and Electro Optical Electronics Module Anodized Field Removable Detector Aluminum Module Puck Rugged superior protection against EMI RFI and handling plus easier field installation...

Page 8: ...ctor may cause the fire to be undetected 4 The Model SM4 is a 316 Stainless Steel Swivel Mount designed for the FSC Detector housing The adapter plate with the two 2 screw holes facing away is attache...

Page 9: ...se Alcohol or IPA sparingly and a cotton swab 3 There are no serviceable parts inside the Detector puck If the puck is opened up or tampered with all warranties are voided FSX Detector Module puck Fig...

Page 10: ...ule puck has a six 6 pin and a ten 10 pin keyed removable connector with screw terminal female plugs that connect to the two 2 respective male connectors with analog digital and relay interfaces see F...

Page 11: ...od wiring practices simplifies installation improves reliability and facilitates maintenance 3 For applications requiring analog digital communications please refer to Section 3 2 of this Instruction...

Page 12: ...ed properly to the correct length loose wire strands must be removed and each wire must be securely and firmly screwed clockwise in the connector 2 If using conduit ensure a proper conduit seal approp...

Page 13: ...ng window lens cleanliness terminal wiring integrity actual relay activation and the proper functionality of any other outputs that are used Also since most detectors are installed in a fire alarm sys...

Page 14: ...red ALARM LED on the face of the Detector slowly move the Test Lamp s boresight to ensure the Detector receives its full intensity UNOTE Practicing this technique may help to optimize testing of the F...

Page 15: ...SP to accurately distinguish radiant energy from a real fire and a false alarm source s Fire Sentry has developed and refined these complex proprietary and patented WideBand IR algorithms over the las...

Page 16: ...y Time OFF ON 20 Sec Verify Time OFF OFF EOL Resistor SW2 6 Enabled ON Disabled OFF Alarm Relay SW2 7 Factory default settings are shown with a gray background Energized ON De Energized OFF Fault Rela...

Page 17: ...l operation the bright Blue LED blinks flashes every 10 seconds See Figure 3 4 for the location of the Blue LED Normal Operation is defined as the Detector with 24 VDC applied and no Alarm or Fault co...

Page 18: ...ion Over Temperature 110 C or 230 F for the Extended Temperature Version Under Temperature 40 C or 40 F for the Standard Version Under Temperature 50 C or 58 F for the Extended Temperature Version One...

Page 19: ...in excess of the purchased price of the product s for any loss of use loss of time inconvenience commercial loss lost profits or savings or other incidental special or consequential damages arising o...

Page 20: ...ss II Groups E F G Class III Approvals FM cFM ATEX IECEx FS24X 211 221 QuadBand Triple IR Detector 110 Filed of View General Applications with Relays 4 20mA Output FireBusII 316 Stainless Steel Enclos...

Page 21: ...ed by something such as a newly installed pipe or duct storage box parked vehicle etc and its alarm outputs are functioning properly For calibrated testing in compliance with NFPA 72 Codes for flame d...

Page 22: ...in X 12 in 0 3m X 0 3m 60 feet 18 meters 5 seconds Paper 24 Standard 8 5 x 11 sheets 90 feet 27 meters 8 seconds Silane 1 foot 0 3 meter Plume 15 feet 4 5 meters 5 seconds The following table provides...

Page 23: ...t 15 24 meters Modulated Sunlight No Alarm 25 feet 7 62 meters Modulated Arcwelding 3 feet 9 inches 1 14 meters Source at 15 feet 4 57 meters Fire at 30 feet 9 14 meters Continuous Arcwelding 3 feet 9...

Page 24: ...DE and OPERATING MANUAL Fire Sentry Corporation Document No 6178 001 Rev Q Copyright 2011 All Rights Reserved Page 21 4 7 Drawings 4 7 1 Outline and Dimensions Figure 4 3 Outline Dimesional Drawing fo...

Page 25: ...and Terminal Connections Figure 4 5 Typical Wiring for 4 20mA Sourcing Analog Output Figure 4 6 Typical Wiring for 4 20mA Sinking Analog Output NOTES 1 Cable shield must be grounded at one end only a...

Page 26: ...9 10 Alarm Fault Input N O Alarm Relay Contacts Fault Relay Contacts N O Note 3 Note 2 Note 4 EOL Note 1 Figure 4 8 Typical Relay Output Wiring for Monitoring Alarm and Fault Contacts on a single two...

Page 27: ...d OPERATING MANUAL Fire Sentry Corporation Document No 6178 001 Rev Q Copyright 2011 All Rights Reserved Page 24 Drawings continued 4 7 3 Detector Label Drawings Figure 4 9 FS24X 9 Label for Hazardous...

Page 28: ...larm Immunity 18 Fault Conditions 13 Fault Relay 7 11 13 Features and Benefits 3 FireBusII 11 12 13 15 16 Flame Response Sensitivity 17 UH Hazardous Locations 1 HART Communication 15 16 High Temperatu...

Reviews: