If the application for the Detector requires different settings, refer to Section 3.2 for detailed descriptions.
U
Before applying 24 VDC power to the Detector, make sure
U
:
1. Wire connections are correct (Section 2.3). Each wire must be stripped properly to the correct length,
loose wire strands must be removed and each wire must be securely and firmly screwed clockwise in
the connector.
2. If using conduit, ensure a proper conduit seal, (appropriate for the area classification), has been
installed and
U
all measures to prevent moisture ingress have been taken
U
.
3. The FSX Detector is securely mounted and has an unobstructed view of the area of coverage
(Section 2.1).
4. The Detector window is unobstructed and clean.
The Detector is now ready for Power-Up.
U
On Power-Up, the Fault Relay will change status if the Factory
Default Setting is used (Section 3.2)
.