Power-limited Wiring Requirements
Standard Relays
The control panel provides three Form-C relays rated for 2.0 amps @ 30 VDC (resistive) and 2.0 amps @ 30 VAC
(resistive).
2.6
Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all
power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or
conduits. A typical wiring diagram for the MS-2410BC is illustrated in Figure 2-9.
FIGURE 2-8:
Relay Terminals
Relay connections may be power-limited or nonpower-limited, provided that a minimum of
0.25" is maintained between conductors of power-limited and nonpower-limited circuits.
Relay contacts shown with no power applied to panel
Relay contacts shown with power applied to panel and
no active troubles, alarms or supervisories
C NC NO C NC NO C NC NO
C NC NO C NC NO C NC NO
FIGURE 2-9:
Typical Wiring Diagram for Power-limited Requirements
Power-limited Circuits
Nonpower-limited
Circuit
Power-limited Circuits
AC Power
Summary of Contents for MS-2410BC
Page 6: ...6 Document 50801 Rev B 8 17 98 P N 50801 B MS 2410BC Terminals and Connectors AC Power ...
Page 56: ...Slide in Labels 56 Document 50801 Rev B 8 17 98 P N 50801 B ...
Page 58: ...Slide in Labels 58 Document 50801 Rev B 8 17 98 P N 50801 B ...
Page 60: ...Slide in Labels 60 Document 50801 Rev B 8 17 98 P N 50801 B ...
Page 61: ...Document 50801 Rev B 8 17 98 P N 50801 B 61 Notes ...
Page 62: ...62 Document 50801 Rev B 8 17 98 P N 50801 B Notes ...
Page 63: ...Document 50801 Rev B 8 17 98 P N 50801 B 63 Notes ...