Installation and Maintenance Instructions for

H355, H355R, and H355HT Intelligent Plug-In Temperature Sensors

This sensor must be installed in compliance with the control panel system installation manual. The installation must
meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed
in compliance with the National Fire Protection Association (NFPA); see NFPA 72.

Before installing sensors,  please read the system wiring and installation manual thoroughly. This manual provides
detailed information on sensor spacing, placement, zoning, and special applications. Copies of these manuals are
available from Fire•Lite.

GENERAL DESCRIPTION

Models H355, H355R, and H355HT are intelligent sensors that utilize a state-of-the-art thermistor sensing circuit for fast
response. These sensors are designed to provide open area protection with 50 foot spacing capability. Model H355 is a
fixed temperature sensor with 135° F fixed temperature alarm. Model H355R is a rate-of-rise temperature sensor with
135° F fixed temperature alarm. Model H355HT is a high temperature sensor with 190° F fixed temperature alarm.

Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is avail-
able as an optional accessory (Part No. RA400Z).

Models H355, H355R, and H355HT require compatible addressable communications to function properly.
Connect these sensors to listed-compatible control panels only.

SPECIFICATIONS

Diameter:

6.1 inches (155 mm) installed in B350LP

Height:

2.1 inches (51 mm)

Weight:

4.8 ounces (137 gm)

Installation Temperature:

–4°F to 100°F (–20°C to 38°C); H355 and H355R
–4°F to 150°F (–20°C to 66°C); H355HT

Operating Humidity Range:

10% to 93% Relative Humidity Noncondensing

Mounting:

B350LP flanged base

Voltage Range:

15 to 32 Volts DC Peak

Standby Current:

300 

µ

A @ 24 VDC (one communication every 5 sec.with LED blink enabled)

LED Current:

6.5 mA @ 24 VDC

Fixed Temperature Rating:

135°F (57°C); H355 and H355R
190°F (88°C); H355HT

Rate of Rise Detection:

Responds to greater than 15°F/min.; H355R

F300-25-00

1

I56-1972-00R

Fire•Lite, One Fire•Lite Place, Northford, CT 06472

Summary of Contents for H355

Page 1: ... temperature alarm Model H355R is a rate of rise temperature sensor with 135 F fixed temperature alarm Model H355HT is a high temperature sensor with 190 F fixed temperature alarm Two LEDs on each sensor light to provide a local visible sensor indication Remote LED annunciator capability is avail able as an optional accessory Part No RA400Z Models H355 H355R and H355HT require compatible addressab...

Page 2: ...ch when activated prevents removal of the sensor without the use of a tool See the installation instruction manual for the sensor base for details in using this feature TESTING SENSITIVITY Before testing notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service Disable the system to prevent unwanted alarms All sensors must be tested after instal...

Page 3: ...s described under MAINTENANCE and retested If the detectors still fail these tests they should be returned for repair Figure 3 Views showing position of test magnet F300 25 00 3 I56 1972 00R LED TEST MAGNET MARKER LED TEST MAGNET MARKER A78 1478 06 A78 1944 02 MAINTENANCE NOTE Before cleaning notify the proper authorities that the system is undergoing maintenance and therefore the system will temp...

Page 4: ...iate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harm ful interference to radio or television reception which can be determined by turning the equipment off and on the user is enc...

Reviews: