36
FCPS-24FS Series Instruction Manual —
P/N 51883:H1 4/14/2011
Applications
Master FCPS-24FS Power Supply Connected to FACP
5.6 Master FCPS-24FS Power Supply Connected to FACP
In this application, a master FCPS-24FS power supply, set for synchronization, is connected to an
FACP with nonsynchronized output.
The following notes apply to this illustration
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Use only devices from the same manufacturer in each system.
5.7 Canadian Applications
Canadian applications, per ULC, require the following:
•
The FCPS-24FS power supply must be used as a Notification Appliance Circuit extender only.
The TB2 terminals cannot be configured as auxiliary power outputs.
•
The host FACP must monitor for all ground fault conditions. The Ground Fault Detection
circuit on the FCPS-24FS power supply must be disabled by cutting jumper JP1.
-
+
TB
4
JP
3
J3
TB
5
TB2
JP
1
JP
2
OU
T
4
-NA
C
4
+
OUT
3
-NAC
3+
OUT
2
-NA
C
2
+
OU
T
1
-NAC1
+
AUX -
IN
2-
IN2+
OUT1-
OUT1+
IN1-
IN1+
SYNC IN -
SYNC IN +
AUX +
NO
NC
AU
X
T
B
L
CO
M
1 2 3 4 5 6 7 8 9 10
8
7
6
5
4
3
2
1
3
2
1
Standby Polarity Shown
FCPS-24FS
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = OFF (master)
4 = OFF (No AC Fail
Reporting Delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.6 Supervised FACP to Master Connections (nonsynchronized source)