Fire-Lite B350LP Installation Instructions Download Page 3

F400-21-00

3

I56-954-01R

3

2

1

3

2

1

3

2

1

+

-

-

+

U.L. LISTED COMP

A

TIBLE

CONTROL

 P

ANEL

CLASS A OPTIONAL WIRING

REMOTE ANNUNCIATOR

+

-

CAUTION: Do not loop wire under terminal 1 or 2.
Break wire run to provide supervision of connections.

A78-1253-00

Figure 3. Typical Wiring Diagram for 2-wire loop

TAMPER-RESISTANCE

Note: Do NOT use the tamper-resistant capability if the XR2 Removal Tool will be used.

The Tamper Resistant Tab, in the Detector Mounting Bracket, can make the detector tamper-resistant by making it nec-
essary to use a small screwdriver or similar tool to detach the detector from the base.

To make the detector tamper-resistant, use needle-nose pliers to break the smaller tab at the scribed line on the tamper
resistant tab. Figures 1 and 4A show the location of this tab on the detector mounting bracket.

To remove the detector from the base after it has been made tamper resistant, remove the decorative ring by rotating it
in either direction and pulling it away from the base. Then, insert a small screwdriver into the notch, as indicated in Fig-
ure 4B, and press the plastic lever toward the mounting surface before rotating the detector counterclockwise for re-
moval.

PLASTIC LEVER

BREAK TAB AT
DOTTED LINE BY
TWISTING TOWARD
CENTER OF BASE.

USE SMALL-BLADED
SCREWDRIVER TO
PUSH PLASTIC LEVER
IN DIRECTION OF
ARROW.

A78-1175-03

Figure 4A. Enabling the

Figure 4B. Removing the Detector

Tamper-Resistant Capability

Head from the Base

Summary of Contents for B350LP

Page 1: ... detectors The B350LP base is intended for use in a 2 wire addressable system with screw terminals provided for power and and remote annunciator connections Communication takes place over the power and lines BASE TERMINALS NO FUNCTION 1 Power Remote Annunciator 2 Power 3 Remote Annunciator A78 1318 00 F400 21 00 1 I56 954 01R Fire Lite Alarms Inc One Fire Lite Place Northford CT 06472 203 484 7161...

Page 2: ...o smaller than AWG 18 However the screws and clamping plate in the base can accommodate wire sizes up to AWG 12 The use of twisted pair wiring or shielded cable for the power and loop is recom mended to minimize the effects of electrical interfer ence If shielded cable is used the shield connection to and from the detector must be continuous by using wire nuts crimping or soldering as appropriate ...

Page 3: ...per resistant use needle nose pliers to break the smaller tab at the scribed line on the tamper resistant tab Figures 1 and 4A show the location of this tab on the detector mounting bracket To remove the detector from the base after it has been made tamper resistant remove the decorative ring by rotating it in either direction and pulling it away from the base Then insert a small screwdriver into ...

Page 4: ... is not acceptable for three stripped wires to be under the same wiring terminal unless they are separated by a washer or a lug like the spade lug supplied with the model RA400Z See Figure 5 for installation A78 1473 00 Figure 5 Connection to Remote Annunciator Terminal STRIPPED WIRE WIRE WITH SPADE LUG F400 21 00 4 I56 954 01R 2000 Fire Lite Please refer to insert for the Limitations of Fire Alar...

Reviews: