Fire-Lite B350LP Installation Instructions Download Page 2

F400-21-00

2

I56-954-01R

MOUNTING

This detector base mounts directly to 3-1/2 inch and 4
inch octagon boxes, 4 inch square boxes (with or with-
out plaster rings) and single gang boxes. To mount, re-
move the decorative ring by turning it in either direction
to unhook the snaps, then separate the ring from the
base. Install the base on the box using the screws sup-
plied with the junction box and the appropriate mount-
ing slots in the base. Place the decorative ring on the
base and rotate it in either direction until it snaps into
place (see Figure 2).

INSTALLATION WIRING GUIDELINES

All wiring must be installed in compliance with all appli-
cable local codes and any special requirements of the
authority having jurisdiction, using the proper wire
size. The conductors used to connect smoke detectors
to control panels and accessory devices should be
color-coded to reduce the likelihood of wiring errors.
Improper connections can prevent a system from re-
sponding properly in the event of a fire.

For signal wiring (the wiring between interconnected
detectors), it is recommended that the wire be no
smaller than AWG 18. However, the screws and
clamping plate in the base can accommodate wire
sizes up to AWG 12. The use of twisted pair wiring or
shielded cable for the power (+ and –) loop is recom-
mended to minimize the effects of electrical interfer-
ence.

If shielded cable is used, the shield connection to and
from the detector must be continuous by using wire
nuts, crimping, or soldering, as appropriate for a reli-
able connection.

Make electrical connections by stripping about 3/8

" (10 mm) of insulation from the end of the wire (use strip gauge

molded in base), sliding the bare end of the wire under the clamping plate, and tightening the clamping plate screw. Do
not loop the wire under the clamping plate.

The zone wiring of the detector base should be checked before the detector heads are installed in them. The wiring
should be checked for continuity and polarity in the base, and dielectric tests should be performed.

The base includes a label for recording the zone, address, and type of detector being installed. This information is impor-
tant to set the address of the detector head that will later be plugged into the base and to verify the type required for that
location.

A78-1175-13

Figure 2. Mounting Detector to Box

SNAP ON
DECORATIVE
RING

SCREWS (NOT
SUPPLIED)

DETECTOR
BASE

BOX (NOT
SUPPLIED)

Summary of Contents for B350LP

Page 1: ... detectors The B350LP base is intended for use in a 2 wire addressable system with screw terminals provided for power and and remote annunciator connections Communication takes place over the power and lines BASE TERMINALS NO FUNCTION 1 Power Remote Annunciator 2 Power 3 Remote Annunciator A78 1318 00 F400 21 00 1 I56 954 01R Fire Lite Alarms Inc One Fire Lite Place Northford CT 06472 203 484 7161...

Page 2: ...o smaller than AWG 18 However the screws and clamping plate in the base can accommodate wire sizes up to AWG 12 The use of twisted pair wiring or shielded cable for the power and loop is recom mended to minimize the effects of electrical interfer ence If shielded cable is used the shield connection to and from the detector must be continuous by using wire nuts crimping or soldering as appropriate ...

Page 3: ...per resistant use needle nose pliers to break the smaller tab at the scribed line on the tamper resistant tab Figures 1 and 4A show the location of this tab on the detector mounting bracket To remove the detector from the base after it has been made tamper resistant remove the decorative ring by rotating it in either direction and pulling it away from the base Then insert a small screwdriver into ...

Page 4: ... is not acceptable for three stripped wires to be under the same wiring terminal unless they are separated by a washer or a lug like the spade lug supplied with the model RA400Z See Figure 5 for installation A78 1473 00 Figure 5 Connection to Remote Annunciator Terminal STRIPPED WIRE WIRE WITH SPADE LUG F400 21 00 4 I56 954 01R 2000 Fire Lite Please refer to insert for the Limitations of Fire Alar...