Fire-Lite Alarms SD355CO Installation And Maintenance Instructions Download Page 3

Parts Per Million

Detector response time, min.

70 ±5ppm

60-240

150 ±5ppm

10-50

400 ±10ppm

4-15

FIGURE 5. SENSOR ASSEMBLY:

Also young children and pets may be the first to be affected.

Per UL standard 2075, the SD355CO has been tested to the sensitivity limits 
defined in UL standard 2034. 

ALARM THRESHOLDS ARE AS FOLLOWS: 

What to do if the carbon monoxide detector goes into alarm: 

Immediately move to a spot where fresh air is available, preferably outdoors. 

IMPORTANT: This detector should be tested and maintained regularly follow-
ing National Fire Protection Association (NFPA) 720 requirements. 

CLEANING

Before removing the detector, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will be temporarily out of 
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.

1.  Remove the sensor to be cleaned from the system.
2.   Remove the sensor cover. Use a small flat blade screwdriver to gently re-

lease each of the four cover removal tabs that hold the cover place. Use 
caution to avoid damaging the thermistors and other sensors (see Figure 5).

3.   Carefully vacuum the outside of the anti insect screen without removing 

it from the detector cover.

4.   The chamber cover, CO and IR sensors may be removed as a single as-

sembly. Gently pull the assembly away from the sensing chamber being 
careful neither to damage the thermistors, the IR / CO sensor PCB nor to 
strain the connector cable to the PCB, then gently folded away from the 
optical chamber.

5.   Use a vacuum cleaner and/or clean compressed air to remove dust and 

debris from the sensing chamber and sensing chamber cover.

6.   Re-install the sensing chamber cover assembly by sliding the cover over 

the chamber, gently pressing it home until it snaps into place.

7.   Re-install the sensor cover. Use the cover removal tabs, LEDs and therm-

istors to align the cover with the sensor. Snap the cover into place.

8.   When all sensors have been cleaned and re-installed, restore power to 

the loop and test the sensor(s) as described under TESTING.

After completion of maintenance and testing, notify the proper authorities 
that the system is operational.

CO SENSOR LIFETIME

The CO cell has an expected lifetime of approximately six years. The detec-
tor is programmed to signal the approach of end of this lifetime to the con-
trol panel. The CO cell is not a field replaceable component and on failure, 
you should contact the system supplier to arrange for replacement of the cell. 
The smoke sensor will continue to operate using the photoelectric sensing 
chamber, thermal and infra-red sensors even though the CO cell is no longer 
operational.  The CO detector will not operate once the CO cell has reached 
its end of life.

SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS

Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

SENSOR COVER

COVER 

REMOVAL 

TABS

THERMISTORS

DETECTOR BASE

IR 

SENSOR

CO 

SENSOR

OPTICAL 

CHAMBER 

COVER

OPTICAL 

CHAMBER 

BASE

C0952-00

FL-400-006  3 I56-4129-000

Many causes of reported carbon monoxide poisoning indicate that while vic-
tims are aware that they are not well, they become so disoriented that they 
are unable to save themselves by either exiting the building or calling for 
assistance. 

Summary of Contents for SD355CO

Page 1: ...move power from the communication line before installing sensors 1 Wire the sensor base supplied separately per the wiring diagram see Figure 1 2 Set the desired address on the sensor address switches see Figure 2 3 Install the sensor into the sensor base Push the sensor into the base while turning it clockwise to secure it in place SPECIFICATIONS Operating Voltage Range 15 to 32 VDC Standby Curre...

Page 2: ... in Figure 3 for 6 12 seconds NOTE If the magnet is held in place for too long the fire alarm test function will be triggered Reset the panel and proceed with testing the CO portion of the device It may be preferred to put the device into fire alarm first via the magnet test to ensure the device has successfully entered test mode 2 Spray a UL approved CO agent into the top ring of the detector s g...

Page 3: ...essed air to remove dust and debris from the sensing chamber and sensing chamber cover 6 Re install the sensing chamber cover assembly by sliding the cover over the chamber gently pressing it home until it snaps into place 7 Re install the sensor cover Use the cover removal tabs LEDs and therm istors to align the cover with the sensor Snap the cover into place 8 When all sensors have been cleaned ...

Page 4: ...iate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installa tion If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is enc...

Reviews: