3.2 Full Supervision via Input Circuit or Monitor Module
This method of supervision provides FACP annunciation of the FCPS trouble condition
even if the FACP is in alarm. The FACP's Notification Appliance Circuit is not used for
supervision. Cut diode D31, jumper JP2 and resistor R63. Monitor FCPS trouble
contacts at terminals TB3-3 and TB3-5. Any trouble condition listed above will trigger
the internal trouble contact regardless of voltage polarity on the input 1. An addressable
monitor module or any FACP input circuit may be used to track the condition of the
trouble contact (refer to Figures 4-4, 4-5 and 4-6).
Figure 3-1: Wiring Diagram of Multiple FCPS Units