94
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Programming
Master Programming Level
ANN-LED Options
Pressing
2
for Module Options while viewing the (XXX) ANN-BUS Address Screen when the ANN-LED
option is selected, will display the following screen:
The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed to annunciate Alarms, Supervisories, and
Troubles for SLC Loop #1 addressable Detectors with addresses 001 through 010. The programming can be changed using ANN-LED
Address Screens 2 and 3.
Pressing
1
while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information.
Pressing
2
while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate only Alarms for addressable
device addresses 001-030 or Alarms, Supervisories, and Troubles for addressable device addresses 001-010.
Pressing
1
while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be annunciated - refer to the tables in
ANN-LED Zone Option - Alarm Only (for use with ANN-RLED module)
Only (for use with ANN-RLED module)
Pressing
2
while viewing ANN-LED Address Screen #3 will select either addressable detectors or addressable modules to be annunci-
ated.
ANN-LED Zone Option - Alarm Only (for use with ANN-RLED module)
If
Zone
is selected as the module option, and the module is programmed to annunciate
alarms only
, the first ten LEDs on the first ANN-
LED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the remain-
ing modules will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED
assignments for each ANN-LED module will be as follows.
The LED assignments for the modules annunciating Zone Ranges 060 - 089 and 090 - 099, will follow the same pattern as the second
ANN-RLED module.
Alarm Silenced
NAC 1 Fault
NAC 2 Fault
NAC 3 Fault
NAC 4 Fault
Earth Fault
Battery Fault
Charger Fault
Disabled
Maintenance
Zone 000
Active/Alarm
Zone 001
Active/Alarm
Zone 002
Active/Alarm
Zone 003
Active/Alarm
Zone 004
Active/Alarm
Zone 005
Active/Alarm
Zone 006
Active/Alarm
Zone 007
Active/Alarm
Zone 008
Active/Alarm
Zone 009
Active/Alarm
Zone 010
Active/Alarm
Zone 011
Active/Alarm
Zone 012
Active/Alarm
Zone 013
Active/Alarm
Zone 014
Active/Alarm
Zone 015
Active/Alarm
Zone 016
Active/Alarm
Zone 017
Active/Alarm
Zone 018
Active Alarm
Zone 019
Active/Alarm
Zone 020
Active/Alarm
Zone 021
Active/Alarm
Zone 022
Active/Alarm
Zone 023
Active/Alarm
Zone 024
Active/Alarm
Zone 025
Active/Alarm
Zone 026
Active/Alarm
Zone 027
Active/Alarm
Zone 028
Active/Alarm
Zone 029
Active/Alarm
Table 3.4 ANN-RLED Module #1
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Zone 030
Active/Alarm
Zone 031
Active/Alarm
Zone 032
Active/Alarm
Zone 033
Active/Alarm
Zone 034
Active/Alarm
Zone 035
Active/Alarm
Zone 036
Active/Alarm
Zone 037
Active/Alarm
Zone 038
Active/Alarm
Zone 039
Active/Alarm
Zone 040
Active/Alarm
Zone 041
Active/Alarm
Zone 042
Active/Alarm
Zone 043
Active/Alarm
Zone 044
Active/Alarm
Zone 045
Active/Alarm
Zone 046
Active/Alarm
Zone 047
Active/Alarm
Zone 048
Active Alarm
Zone 049
Active/Alarm
Zone 050
Active/Alarm
Zone 051
Active/Alarm
Zone 052
Active/Alarm
Zone 053
Active/Alarm
Zone 054
Active/Alarm
Zone 055
Active/Alarm
Zone 056
Active/Alarm
Zone 057
Active/Alarm
Zone 058
Active/Alarm
Zone 059
Active/Alarm
Table 3.5 ANN-RLED Module #2
ANN XXX
1=ENABLED YES
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN XXX Screen #2
ANN-LED - ADDR X-1
SLC 1 DET 001-010
ALARM, TRBL, SUPV
ANN-LED Address Screen #1
ANN-LED - ADDR X-1
1=POINT/ZONE POINT
2=ALARM/ATS ATS
ANN-LED Address Screen #2
ANN-LED - ADDR X-1
1=RANGE PT001-010
2=DET/MOD DET
ANN-LED Address Screen #3