62
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Programming
Master Programming Level
Type Monitor
Using the FS-Tools Upload/Download utility, unique user-defined monitor types can be created and loaded
into the FACP for later use. The FACP response to the activation of a user-defined type is the same as most
previous standard types in the list, thus allowing a variety of user-defined types and responses. To select the
type of monitor module being programmed, press the
2
key while viewing the Edit Monitor Screen #2. This
will cause the control panel to display the following Monitor Type Screens:
Pressing the down arrow key will display additional Monitor Type screens. While viewing one of the Monitor Type screens, select the
type of monitor module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Moni-
tor Screen #2 which will show the new type selection.
Table 3.1 lists the Monitor Types and their respective functions.
Monitor module type selection will affect the function of the point as follows:
Monitor Type
Action When Activated
Pull-Station
Fire Alarm
User-Defined-1
same as previous (Pull-Station)
Waterflow
Fire Alarm Delayed
User-Defined-2
same as previous (Waterflow)
Monitor
Fire Alarm
User-Defined-3
same as previous (Monitor)
Future
not used
Future
not used
Smoke-Conventional
Fire Alarm
User-Defined-5
same as previous (Smoke-Conventional)
Heat Conventional
Fire Alarm
User-Defined-6
same as previous (Heat-Detector)
Medic Alert
1
General Purpose Signaling, latching
User-Defined-7
same as previous (Medic-Alert)
Hazard Alert
General Purpose Signaling, latching
User-Defined-8
same as previous (Hazard-Alert)
Tornado Alert
General Purpose Signaling, latching
User-Defined-9
same as previous (Tornado-Alert)
Phone
Active Phone (LCD display only)
User-Defined-10
same as previous (Phone)
Tamper
Supervisory, nonlatching (tracking)
User-Defined-11
same as previous (Tamper)
Supervisory
Supervisory, latching
User-Defined-12
same as previous (Supervisory)
Supervisory AR
2
Supervisory, nonlatching (tracking)
User-Defined-13
same as previous (Supervisory-AR)
HVAC OVRRIDE
3
Switch Supervisory, nonlatching (tracking)
Power Monitor
Power Fault
User-Defined-14
same as previous (Power Monitor)
Trouble Monitor
Trouble
User-Defined-15
same as previous (Trouble Monitor)
Process Monitor
General Purpose Signaling, latching
User-Defined 16
same as previous (Process-Monitor)
Process-Monitor-AR
General Purpose Signaling, nonlatching (tracking)
User-Defined-17
same as previous (Process-Monitor-AR)
MNS Event
Allows the Mass Notification System to override FACP programming and
turn off designated active outputs
User-Defined-18
same as previous (MNS Event)
Table 3.1 Monitor Types
EDIT MONITOR
1=ENABLED
2=TYPE MONITOR
Edit Monitor Screen #2
MONITOR TYPE
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
Monitor Type Screen #1