BG-12L Manual Pull Station

Patented, U.S. Patent No. Des. 428,351; 6,380,846; Other Patents Pending

Document 50964 

I56-2263-004

Description
The BG-12L pull station is a non-coded, dual-action manual pull station with a key-lock 

reset feature. It provides Fire•Lite control panels with one normally open (N/O) alarm initi

-

ating input. The BG-12L meets the ADAAG controls and operating mechanisms guidelines 

(section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate 
the pull station. Operating instructions are molded into the pull station handle along with 
Braille text. Molded Terminal numbers are also present.

Ratings 

Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or 
DC).

Installation

The BG-12L pull station can be surface mounted to an SB-10 or SB-I/O surface backbox 
or semi-flush mounted on a standard single-gang, double-gang or 4

 (10.16 cm) square 

electrical box. The optional BG-TR trim ring can be used if the BG-12L is to be semi-flush 

mounted.

Operation

To activate the dual-action pull station, push in and pull down on the handle. The word 

‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta

-

tion is reset.

The  pull  station  includes  one  Single  Pole,  Single Throw  (SPST)  Normally  Open  (N/O) 

switch which closes upon activation of the pull station.

Resetting the Pull Station

1.  Insert the key into the lock and rotate 1/4 turn counterclockwise.
2.  Open the door until the handle returns to normal.
3.  Close and lock the door.

Note:

  Closing the door automatically resets the switch to the ‘Normal’ position. Opening 

the door will not activate or deactivate the alarm switch.

STRIP GAUGE

1        2       3      4

IDC –

FROM  

FACP +

TO NEXT

DEVICE

– IDC

+

WARNING: DO NOT LOOP WIRING 

UNDER ANY TERMINALS. BREAK WIRE 

RUN TO MAINTAIN IDC SUPERVISION.

P0205-00

Wiring

CAUTION! Do not detach the door of the pull station during installation. The door of 

the pull station cannot be reattached to the backplate after the backplate has already been 
installed onto an electrical box.

CAUTION!

Install  the  Fire•Lite  BG-12L  pull  station  in  accordance  with  these  instructions, 

 

applicable NFPA standards, national and local Fire and Electrical codes and the requirements 
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con

-

ducted in accordance with the appropriate NFPA standards. Failure to follow these directions 
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for 

 

devices that have been improperly installed, tested or maintained.

ADA Compliance

For ADA compliance, if the clear floor space only allows forward approach to an object, the 
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space 
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is 
54 inches (137.16 cm).

BG-12L

Manual Pull Station

WARNING!  Do not loop wiring under any 

terminals. Break wire run to 
maintain IDC supervision.

Document 50964 

I56-2263-004

P0194-01