Page 2 of 4  —  DF-50934

SPECIFICATIONS
Operational

Range:

  30' to 330' (length).

Smoke detector spacing:

  On smooth ceilings, 60' be-

tween projected beams and not more than one-half that

spacing between a projected beam and a sidewall.  Other

spacing may be used depending on ceiling height, airflow

characteristics, and response requirements.  See NFPA

72 A-5-3.5.5.2.

Sensitivity:

  30% ± 5% total obscuration 

OR 

55% ± 5%

total obscuration.

Fault condition (Trouble):

  95% or more obscuration;

automatic gain control limit; improper initial alignment.

Test/Reset features:

  Obscuration filter; local reset switch;

remote test and reset switch capability (compatible with

RTS451 test station).

Indicators:

ALARM  —  Local red LED

TROUBLE  —  Local amber LED

NORMAL  —  Local flashing green LED

Alignment aid:

  Integral signal strength indication (4 red

LEDs).

Relays:

  Alarm, Trouble.  EOL relay is required to super-

vise power.

Environmental

Temperature:

  -30°C to 55°C (-22°F to 131°F).

Humidity:

  95% RH non-condensing.

Mechanical

Dimensions:

  With no bracket, 2.5"H x 8.5"W x 7"D.

With ceiling mount bracket, 5.5"H x 8.5"W x 7"D.

With wall mount bracket, 5.5"H x 8.5"W x 10"D.

Weight:

  Receiver, 1.5 lb. (663 g).  Transmitter, 1.3 lb.

(598 g).

Mounting:

  Separate ceiling and wall brackets.

Wiring:

  Plug with attached cable.

Electrical (Receiver)

Voltage:

  20 to 32 VDC.

Maximum ripple voltage:

  30% of nominal (peak to peak).

Current (24 VDC):

Standby:

  10.0 mA maximum.

Alarm:

  28.4 mA maximum.

Trouble:

  27.1 mA maximum.

Start-up surge:

  19.0 mA maximum.

Relay contacts:

  0.5 A at 30 VAC/DC.

Reset time:

  0.6 seconds maximum.

Start-up time:

  1 minute maximum (after 5 minute reset).

Power loss:

  Retain memory for 5 minute minimum.

Electrical (Transmitter)

Voltage:

  18.8 to 32.0 VDC.

Maximum ripple voltage:

  30% of nominal (peak to peak).

Current (24 VDC, 

standby and alarm

):

  10.0 mA max.

ENGINEERING SPECIFICATIONS

The projected beam type smoke detector shall be a 4-wire

24 VDC device to be used with UL listed separately sup-

plied four-wire control panels only.  Unit shall be listed to

UL 268 and shall consist of a separate transmitter and

receiver capable of being powered separately or together.

The detector shall operate in either a short range (30' -

100') or long range (100' - 330') mode.  The temperature

range of the beam shall be -22°F to 131°F.  The detector

shall feature a bank of four alignment LEDs on both the

receiver and transmitter that are used to ensure proper

alignment of unit without special tools.  Beam detector

shall feature automatic gain control which will compensate

for gradual signal deterioration from dirt accumulation on

lenses.  Unit shall include both ceiling and wall mounting

brackets.  Testing shall be carried out using calibrated test

filters or magnet activated remote test station.