Fire Fighting Enterprises FIRERAY 2000 EExd Installation Manual Download Page 5

FIRERAY 2000 EExd 

Hazardous Area Smoke Detector    

  Installation Guide  

 

 

Page 5 of 14 

 
** See specification on page 13 for technical details                                        23989.00.C  (25.08.05) 

To achieve maximum EMI rejection, use screened cables for the system wiring, properly terminated at 
metal glands (Do not use screen pigtails). MICC cable is recommended. 
 
Use the correct EExd approved cable gland types for all system parts in the hazardous area.  
 
Cables must be suitable for a minimum temperature of 101°C. 
 
 

SETTING UP AND ALIGNING - DIRECT BEAM MODE 

 
The Transmitter and Receiver heads must be positioned on 

stable, solid

 

facing surfaces

, such as 

parallel walls, approx 0.3m to 0.6m below the area ceiling (See application notes near the end of this 
guide). The surfaces must be parallel, vertically and horizontally within approx 20 degrees, although a 
greater positioning range is possible (up to 40 degrees off line-of-sight) if the Receiver is also fitted it 
with an Adjustable Mounting Bracket. This is available as an optional extra. If only small adjustments 
are required, the Receiver line-of-sight may be adjusted by fitting spacer washers to it’s wall fixing 
screws, between the Receiver Case and the mounting surface. (Some applications may require 
fabrication of angled mounting brackets etc, in order to cope with awkward wall positions etc. These 
are not supplied). 
 
Install all required cabling to the defined positions for each system part. (See wiring diagram on 
following page, for a typical installation). Ensure compliance with all regulatory and local 
requirements for Hazardous Areas and Fire Alarm Systems. Approved screened cables and approved 
EExd glands and termination methods must be used. Glands at the Controller, Rx and Tx must be 
metal EExd types. The Cable screens or jackets must be terminated properly at the glands, with a 360

°

 

termination. Screen Pigtails must not be used. 
 
Mount the Receiver first, such that it faces, and has un-obstructed line of sight with the expected final 
Transmitter position. Remove the Receiver housing top  (using 5mm Allen key provided). Connect the 
system cabling to the 3 way terminal block on the internal pcb. It is recommended that the External 
Earth point be used on the Tx and Rx housings, to minimise wiring lengths. This must be taken to the 
nearest suitable building Earth point. Alternatively, the housing’s Internal Earth stud may be 
connected, via an additional cable core and connected back at the Control Unit Earth. (see wiring 
diagram on the following page for connections and earthing regimes). Check the connections and 
tighten the cable glands, then refit the housing top, taking care to position the ‘O’ ring seal correctly, 
just below the flange. Tighten the 4 securing screws firmly. 

For safety reasons, and to give the best 

EMI rejection, do not omit any of the Earth connections. 

 
Fit the Transmitter head in a position which aligns as closely as possible with the Receiver line of 
sight, making use of the adjustment bracket provided. A 12mm AF spanner/wrench is required for the 
adjustment bolts. Remove the Transmitter housing top (using 5mm Allen key provided) and set the 
Range Switch to the correct or next higher setting, to match the expected operating range. Use a biro 
tip to set the switches. The switches are ‘ON’ when moved outward, and ‘OFF’ when moved inward, 
toward the housing centre. Note that only one setting must be selected ‘ON’. Connect the system 
cabling to the 3 way terminal block on the internal pcb and Earth the unit housing in the same manner 
as used for the Rx (see wiring diagram on the following page for connections and earthing regimes). 
Check the connections and tighten the cable glands, then refit the housing top, taking care to position 
the ‘O’ ring seal correctly, just below the flange. Tighten the 4 securing screws firmly. 

For safety 

reasons, and to give the best EMI rejection, do not omit any of the Earth connections. 

 
Install and wire the Controller unit in it’s defined position,

 outside

 the hazardous area. Set the unit’s 

Alarm threshold to 25%, 35% or 50%.

 Only close one switch position, for the desired threshold

. Set 

the ‘ALARM LATCH’ switch as required. Switch Closed = latching Fire Alarm operation. For UK 

Summary of Contents for FIRERAY 2000 EExd

Page 1: ...compared to a system utilising flameproof enclosures for all component parts The maximum lateral beam coverage is 15m per Fireray System installed Once installed the Transmitter Head projects a modul...

Page 2: ...s threshold setting and should the signal be reduced below the set threshold the FIRE ALARM relay will be activated within approx 12 seconds Three user selectable threshold setting are available Note...

Page 3: ...nal strength and can be monitored using a voltmeter Controller Unit System Resetting The system can be reset in any of three ways as follows Using the RESET switch in the Controller Unit Normally only...

Page 4: ...regarding both fire alarm systems and EExd IIB applications are adhered to Choose solid stable surfaces on which to mount the Receiver and Transmitter If one of the mounting surfaces for the Transmitt...

Page 5: ...sition Remove the Receiver housing top using 5mm Allen key provided Connect the system cabling to the 3 way terminal block on the internal pcb It is recommended that the External Earth point be used o...

Page 6: ...ext to each other as close as possible and adjusted such that both point at the prisms Choose Receiver and Transmitter mounting surfaces that are parallel to the prism mounting surface within 20 If gr...

Page 7: ...voltmeter 10Vdc range or autorange connected to the Controller unit s METER and terminals Whilst observing the meter reading adjust the Transmitter to prism alignment to achieve the highest reading po...

Page 8: ...technical details 23989 00 C 25 08 05 To check that the beam is being reflected by the prisms rather than some other reflective surface block off the beam completely at the prisms using a suitable no...

Page 9: ...c ALARM N C CO N O N C CO F A U L T A L A R M SIGNAL LEVEL COMP 25 35 50 EExd GLAND EExd GLAND METAL GLAND METAL GLAND METAL GLAND METAL GLAND OPTIONAL REMOTE RESET WIRING SEE TEXT CLOSE TO RESET HAZA...

Page 10: ...to avoid obscuring optical components Internal Earth stud will be found in one of these two positions External Earth terminal will be found in one of these two positions User wiring terminals Wire on...

Page 11: ...o positions User wiring to enter here via suitable EExd IIB or IIC approved gland VIEW INSIDE RECEIVER UNIT WITH TOP WINDOW SECTION REMOVED SHOWING TERMINALS AND SETTINGS ETC note some components not...

Page 12: ...as an apex roof Note 3 No more than 3m of the beam path should be within 500mm of any wall or partitions When Firerays are mounted in the apex the horizontal distance may increase by 1 for each degre...

Page 13: ...supply voltage Control Rx 0 5V p p min sine 50 100Hz 11 5Vdc Immunity increases with higher supply voltage SYSTEM RESET Internal Via slider switch in controller unit External 1 Remote Reset input Gro...

Page 14: ...fication on page 13 for technical details 23989 00 C 25 08 05 Fire Fighting Enterprises Ltd 9 Hunting Gate Hitchin Hertfordshire SG4 0TJ England Tel 44 0 845 4024242 Fax 44 0 845 4024201 Email sales f...

Reviews: