** See specification on page 13 for technical details                                        23989.00.C  (25.08.05) 

 
 
 
Two possible actions are selectable, once the system has exhausted all compensation steps, as follows:- 
 

• 

Leave the COMP switch in the Controller unit OPEN for BS5839 installations (UK). This 
setting allows generation of a FIRE ALARM after reaching the compensation limit, even 
though a FAULT ALARM will be active. This is the only time Fire and Fault indications 
can occur together. 

 

• 

Close the COMP switch if it is required that  FIRE ALARM generation is inhibited once a 
FAULT ALARM has occurred, due to reaching compensation limit. 

 

Controller Unit - Relay Outputs 

The Controller Unit has two sets of outputs for Fire and Fault indication, in the form of voltage free 
single pole changeover relay contacts. The FIRE relay may be set to give either latching or non-
latching operation, determined by a switch (ALARM LATCH) on the Controller pcb. With the switch 
closed, latching operation is selected. 
 

Controller Unit - Signal Strength Metering 

A ‘Metering ‘ output is also provided, to assist with installation. This gives a dc voltage which is 
proportional to the received signal strength and can be monitored using a voltmeter. 
 

Controller Unit - System Resetting 

The system can be reset in any of three ways, as follows :- 
 

• 

Using the RESET switch in the Controller Unit (Normally only used during installation). 

• 

By taking the External Reset input low (to system 0V) for at least 5mS. 

• 

By de-powering the system for 1 second, then re-powering. 

 
Following a reset the system takes 50 seconds to self-calibrate. During this time the Fireray adjusts it’s 
100% signal reference level and so must have a clear unobstructed beam. No tests should be carried 
out until this initialisation period has elapsed. 
 

Notes On Resetting Using The Internal  RESET Switch 
Note that for correct operation, the internal RESET switch must not be set to OFF whilst either of 
the HIGH or LOW signal lamps in the Controller  Unit are illuminated. The gain must be set 
correctly to extinguish both lamps first. If this is not done the system AGC is locked and will not 
operate. (This does not apply to the other two reset methods). 
 
SUMMARY OF SYSTEM CONDITIONS :- 
 
Possible Causes of FAULT Alarms 
 

• 

Controller Unit RESET switch in ON position. 

• 

Controller Unit EXTERNAL RESET input active ( at 0V) 

• 

No power to Controller unit 

• 

No Power to Tx unit 

• 

Beam obscuration >93% for >5 seconds (for whatever reason) 

• 

Tx or Controller power cable break. 

• 

Receiver Signal cable break. 

• 

AGC at limit of compensation. 

• 

Rx/Tx Mis-alignment causing low signal strength 

Summary of Contents for FIRERAY 2000 EExd

Page 1: ...compared to a system utilising flameproof enclosures for all component parts The maximum lateral beam coverage is 15m per Fireray System installed Once installed the Transmitter Head projects a modul...

Page 2: ...s threshold setting and should the signal be reduced below the set threshold the FIRE ALARM relay will be activated within approx 12 seconds Three user selectable threshold setting are available Note...

Page 3: ...nal strength and can be monitored using a voltmeter Controller Unit System Resetting The system can be reset in any of three ways as follows Using the RESET switch in the Controller Unit Normally only...

Page 4: ...regarding both fire alarm systems and EExd IIB applications are adhered to Choose solid stable surfaces on which to mount the Receiver and Transmitter If one of the mounting surfaces for the Transmitt...

Page 5: ...sition Remove the Receiver housing top using 5mm Allen key provided Connect the system cabling to the 3 way terminal block on the internal pcb It is recommended that the External Earth point be used o...

Page 6: ...ext to each other as close as possible and adjusted such that both point at the prisms Choose Receiver and Transmitter mounting surfaces that are parallel to the prism mounting surface within 20 If gr...

Page 7: ...voltmeter 10Vdc range or autorange connected to the Controller unit s METER and terminals Whilst observing the meter reading adjust the Transmitter to prism alignment to achieve the highest reading po...

Page 8: ...technical details 23989 00 C 25 08 05 To check that the beam is being reflected by the prisms rather than some other reflective surface block off the beam completely at the prisms using a suitable no...

Page 9: ...c ALARM N C CO N O N C CO F A U L T A L A R M SIGNAL LEVEL COMP 25 35 50 EExd GLAND EExd GLAND METAL GLAND METAL GLAND METAL GLAND METAL GLAND OPTIONAL REMOTE RESET WIRING SEE TEXT CLOSE TO RESET HAZA...

Page 10: ...to avoid obscuring optical components Internal Earth stud will be found in one of these two positions External Earth terminal will be found in one of these two positions User wiring terminals Wire on...

Page 11: ...o positions User wiring to enter here via suitable EExd IIB or IIC approved gland VIEW INSIDE RECEIVER UNIT WITH TOP WINDOW SECTION REMOVED SHOWING TERMINALS AND SETTINGS ETC note some components not...

Page 12: ...as an apex roof Note 3 No more than 3m of the beam path should be within 500mm of any wall or partitions When Firerays are mounted in the apex the horizontal distance may increase by 1 for each degre...

Page 13: ...supply voltage Control Rx 0 5V p p min sine 50 100Hz 11 5Vdc Immunity increases with higher supply voltage SYSTEM RESET Internal Via slider switch in controller unit External 1 Remote Reset input Gro...

Page 14: ...fication on page 13 for technical details 23989 00 C 25 08 05 Fire Fighting Enterprises Ltd 9 Hunting Gate Hitchin Hertfordshire SG4 0TJ England Tel 44 0 845 4024242 Fax 44 0 845 4024201 Email sales f...

Reviews: