Fire Fighting Enterprises FIRERAY 2000 EExd Installation Manual Download Page 1

FIRERAY 2000 EExd 

Hazardous Area Smoke Detector    

  Installation Guide  

 

 

Page 1 of 14 

 
** See specification on page 13 for technical details                                        23989.00.C  (25.08.05) 

♦ 

   KEY FEATURES

 

⇒ 

Flameproof  Receiver and Transmitter 

⇒ 

Standard Fireray Controller Unit 

⇒ 

High Coverage - up to 1500

2

m  per system 

⇒ 

Low Cost 

⇒ 

Beam Range 10 metres to 100 metres, in 
normal use, 3m to  30 m retro operation. 

⇒ 

12 Volts dc to 24 Volts dc operation 

⇒ 

Selectable Alarm Thresholds 

⇒ 

Low Current Consumption 

⇒ 

Manual or Automatic Fire Alarm Reset 

⇒ 

Automatic Fault Alarm Reset 

⇒ 

Ground Level Electronics 

⇒ 

Extremely Rugged 

⇒ 

Easy installation 

⇒ 

Low maintenance 

♦ 

APPLICATIONS

 

⇒ 

Zone 1 Environments  

⇒ 

Refineries 

⇒ 

Mills 

⇒ 

Munitions Factories 

⇒ 

Munitions Stores 

⇒ 

Flammable Liquid Stores 

⇒ 

Flammable Gas Stores 

⇒ 

Flammable Powder Stores 

⇒ 

Industrial Plants  

⇒ 

Power  Stations 

⇒ 

Warehouses 

⇒ 

Applications requiring highly rugged 
detector heads 

 

 

DESCRIPTION

 

The 

FIRERAY 2000 EExd SMOKE DETECTOR SYSTEM

 is designed primarily to protect EExd, IIB 

hazardous areas. 
 
It consists of a standard Fireray 2000 Controller/Analyser, combined with highly rugged flameproof 
Transmitter and Receiver heads. 
 
The Transmitter and Receiver Heads are designed to be mounted within the protected hazardous area, 
whilst the Analyser is housed outside it. Using the Standard Analyser unit in this way allows a 
significant cost reduction when compared to a system utilising flameproof enclosures for all 
component parts. The maximum lateral beam coverage is 15m per Fireray System installed. 
 
Once installed, the Transmitter Head projects a modulated Infra-Red Beam across the protected area, to 
the Receiver head mounted opposite. The received signal strength is monitored and analysed in the 
Ground Level Controller. Should the beam strength fall below the preset threshold for more than 8 -10 
seconds, a Fire Alarm is signalled to the Control Equipment. The analyser also incorporates monitoring 
for cable breaks or loss of function at the Transmitter or Receiver. If the signal strength is reduced 
suddenly (<5 seconds) by greater than 93% a Fault Alarm is indicated to the Control equipment. The 
Fire and Fault Alarm outputs are provided via two sets of Voltage-Free change-over relay contacts. 
 
The Fire Alarm Relay may be set for latched or auto-reset operation as desired. The Fault Alarm is 
designed to auto-reset once the signal is returned to serviceable limits.   
 
The system may be used with ‘intelligent’ or ‘non-intelligent’ systems. Due to the very low current 
consumption, back-up battery life is extended and the system may be powered from alarm loop 
supplies in most cases. 

 

PARTS LIST 

 

         1 x Transmitter Head (With Clear Lens) 
         1 x Receiver Head (With Dark Lens) 
         1 x Controller/Analyser Unit 
         1 x Adjustable Head Mounting Bracket 

         1 x  Test Filter 
         1 x Installation Guide (This document)           
         1 x Atex Addendum Sheet 0600-(issue) 
         2  x Allen keys (5mm & 10mm)

         1 x Bag of Bracket Fixings 

Summary of Contents for FIRERAY 2000 EExd

Page 1: ...compared to a system utilising flameproof enclosures for all component parts The maximum lateral beam coverage is 15m per Fireray System installed Once installed the Transmitter Head projects a modul...

Page 2: ...s threshold setting and should the signal be reduced below the set threshold the FIRE ALARM relay will be activated within approx 12 seconds Three user selectable threshold setting are available Note...

Page 3: ...nal strength and can be monitored using a voltmeter Controller Unit System Resetting The system can be reset in any of three ways as follows Using the RESET switch in the Controller Unit Normally only...

Page 4: ...regarding both fire alarm systems and EExd IIB applications are adhered to Choose solid stable surfaces on which to mount the Receiver and Transmitter If one of the mounting surfaces for the Transmitt...

Page 5: ...sition Remove the Receiver housing top using 5mm Allen key provided Connect the system cabling to the 3 way terminal block on the internal pcb It is recommended that the External Earth point be used o...

Page 6: ...ext to each other as close as possible and adjusted such that both point at the prisms Choose Receiver and Transmitter mounting surfaces that are parallel to the prism mounting surface within 20 If gr...

Page 7: ...voltmeter 10Vdc range or autorange connected to the Controller unit s METER and terminals Whilst observing the meter reading adjust the Transmitter to prism alignment to achieve the highest reading po...

Page 8: ...technical details 23989 00 C 25 08 05 To check that the beam is being reflected by the prisms rather than some other reflective surface block off the beam completely at the prisms using a suitable no...

Page 9: ...c ALARM N C CO N O N C CO F A U L T A L A R M SIGNAL LEVEL COMP 25 35 50 EExd GLAND EExd GLAND METAL GLAND METAL GLAND METAL GLAND METAL GLAND OPTIONAL REMOTE RESET WIRING SEE TEXT CLOSE TO RESET HAZA...

Page 10: ...to avoid obscuring optical components Internal Earth stud will be found in one of these two positions External Earth terminal will be found in one of these two positions User wiring terminals Wire on...

Page 11: ...o positions User wiring to enter here via suitable EExd IIB or IIC approved gland VIEW INSIDE RECEIVER UNIT WITH TOP WINDOW SECTION REMOVED SHOWING TERMINALS AND SETTINGS ETC note some components not...

Page 12: ...as an apex roof Note 3 No more than 3m of the beam path should be within 500mm of any wall or partitions When Firerays are mounted in the apex the horizontal distance may increase by 1 for each degre...

Page 13: ...supply voltage Control Rx 0 5V p p min sine 50 100Hz 11 5Vdc Immunity increases with higher supply voltage SYSTEM RESET Internal Via slider switch in controller unit External 1 Remote Reset input Gro...

Page 14: ...fication on page 13 for technical details 23989 00 C 25 08 05 Fire Fighting Enterprises Ltd 9 Hunting Gate Hitchin Hertfordshire SG4 0TJ England Tel 44 0 845 4024242 Fax 44 0 845 4024201 Email sales f...