Instructions, Maintenance and Service Manual ULTRAFREEZER Series
15
10.
TROUBLE SHOOTING
10.1
TROUBLE SHOOTING AIRCOOLED CONDENSER
Doesn't reach set
temperature.
Check settings of
the temperature-
controller.
Listen to strange
sounds.
Check operation
of the compressor
of the 1st stage,
fan & compressor
2nd stage.
Check and measure:
Leakage 1st stage,
Refrigerant 2nd stage,
Choked up 2nd stage by moisture or oil.
Cold
-85
-75
Control
-80
-70
Back up
-60
-50
Warm
-70
-60
Change settings.
Wrong
Allright
None
Total failure of
display.
Check power
supply.
Wrong
Wrong
Check fuse.
Check both compressors
& rimheating for circuiting
with regard to earth.
None
Short-circuit
Trace & correct.
Indeed
Voltage on
temperature
controller.
Replace
temperature
controller or
internal fuse.
Indeed
Indeed
Check and measure (1st stage):
Supply voltage,
Relay 1st stage,
“Cool”-relay at temperature controller,
Pressostate,
Startrelay,
Startcapacitor,
Runcapacitor,
Clixon (overheat protection),
Defective compressor.
Ambient temperature too high,
Condenser dirty,
Pressostate 1st stage defect.
Check voltage at fan outlet,
Check fan.
Compressor 1st stage commutes
(on-off-on-off), compressor
2nd stage off & fan operates.
Compressor 1st stage commutes
(on-off-on-off), compressor
2nd stage off & fan doesn't operate.
Check and measure (2nd stage):
Supply voltage,
Startpressure controller settings too high,
Pressostate (settings),
Thermostat (settings),
Startrelay,
Startcapacitor,
Runcapacitor,
Clixon (overheat protection),
Check leakage of refrigerant 1st stage.
Check and measure (2nd stage):
Relay 2nd stage,
Timerelay (time delay),
Pressostate (settings),
Thermostat (settings),
(thermostat not activated, check leakage of
refrigerant 1st stage)
Startrelay,
Startcapacitor,
Runcapacitor,
Clixon (overheat protection),
Defective compressor.
Compressor 2nd stage doesn’t
operate, compressor 1st stage &
fan are operating
Compressor 1st stage ,fan &
compressor 2nd stage are operating
Compressor 1st stage + compressor
2nd stage don't operate,
fan does operate.
Compressor 2nd stage commutes
(on-off-on-off), compressor 1st stage
& fan are operating.