background image

                                                                                            1 

XMT*-JK408 series four-way temperature controllers 

Instruction manual 

Summary 

XMT*-JK408 series intelligent temperature control instrument is a new meter to meet the 

market needs. The meter is controlled by single chip microcomputer, every channel setting value 

and some parameters can be set up independently. It has the advantages of small volume, low 

power consumption, simple operation, easy control, stable operation, reliable, economical 

characteristics. It is widely used in the temperature automatic control systems of machinery

chemical

ceramics

light industrial

metallurgy

petrifaction and heat treatment, and so on.   

 

Primary technical standard: 

1

 

Input signal

:

 CU50

-50.0

150.0℃

Pt100

-19.9

600.0℃

 

K

0

1300℃

E

0

700.0℃

J

0

900.0℃

 

2

Accuracy: 

±0.5%F.S±1B    Cold end compensating deviation

±2℃ 

3

Relay output contact capacity: AC220V/5A (resistance load) or AC220V/0.3A (perceptual load) 

4

Driving solid relay signal output: driving electric current

15mA, voltage

9V. 

5

Control mode: difference control-on/off and PID control 

6

Input power: AC85~242V    50/60Hz 

7

Environment Temperature: 0 to 50℃,    Humidity: ≤85%RH   

 

Instrument panel instruction(consult) 

 

ALM1

ALM4

The first channel to the four channel alarm output indicator light ( red)

 

OUT1

OUT4

The first channel to the four channel control output indicator light ( green )

 

CH1

CH4 key: The first channel to the four channel corresponding channel parameter setting key

 

SET key

Function setting key

                ◄ key

  Shift key

     

▼ key

  Data decrease key

                    ▲ key

  Data increase key

       

 

M

odel significance

: 

         

XMT 

-

    JK 4     

      8     

□    □ 

                        (1)     (2)  (3)  (4)  (5)   (6)

 

Meter faceplate and Installation dimension(mm)

160

×

80

×

130

    152

×

76

 

Design  serial  number

Four  channel  independent  control  meter,  PID  and  ON/OFF  control  can 

www.finglai.com

Summary of Contents for XMT*-JK408 Series

Page 1: ... Cold end compensating deviation 2 3 Relay output contact capacity AC220V 5A resistance load or AC220V 0 3A perceptual load 4 Driving solid relay signal output driving electric current 15mA voltage 9V 5 Control mode difference control on off and PID control 6 Input power AC85 242V 50 60Hz 7 Environment Temperature 0 to 50 Humidity 85 RH Ⅲ Instrument panel instruction consult ALM1 ALM4 The first ch...

Page 2: ...ion alarm 4 negative deviation alarm 5 outside the interval alarm 6 inside the interval alarm 1 3 t Output cycle 0 120 S relay control action cycle setting 10 S 4 dp Display accuracy 0 1 1 have radix point 0 have not radix point 0 5 P SH The max value of temperature range P SH P SL They are used to reset proper temperature range as per user s application As for the Max temperature range for differ...

Page 3: ... and parameter value times will be shown respectively about CH1 window and CH2 window you can adjust these parameters by pressing and save the setting by press SET key every parameter should be saved after setting then enter next parameter set 6 3 You can press CH1 CH2 CH3 CH4 for 3 seconds to enter into corresponding channel menu After finished one parameter set press SET to save it then enter in...

Page 4: ...in the daily application Sheet8 1 Common fault disposal Fault symptom Analysis of causes Disposal measurement Abnormal power 1 Poor contact of power cord 2 Power switch without lose Check the power Signal display do not correlate with the facts display HH or LL 1 Sensor model mismatch 2 Wrong signal connect ion 1 Check sensor model and meter interior input parameter 2 Check signal wire Abnormal co...