Fimer VSN300 Quick Installation Manual Download Page 7

7

9.  Identification label

This label is necessary to remember all the identification data of VSN300 WIFI LOGGER CARD and it should be applied in the dedicated area shown 

below. 

 

FIMER
VSN300 WIFI LOGGER CARD

SN: YYWWSSSSSS

MAC:  XX:XX:XX:XX:XX:XX

PRODUCT KEY:  XXXX - XXXX - XXXX - XXXX

APPLY HERE THE

 IDENTIFICATION LABEL

 ATTENTION – 

A

Save these instructions! The information on the above label will be used by Technical Service in case of problems.

10.  Characteristics and technical data

VSN300 WIFI LOGGER CARD

Communication

Inverter interface

Hyperlink (CAN@1 Mbps + RS485@115 kBaud) / Legacy (Serial link TTL @ 19.2 KBaud)

User interface

Wi-Fi Certified™ IEEE 802.11 b/g/n (2,4 GHz)

Communication Protocols

LAN/WAN protocols

HTTPS, DHCP, NTP, SSL, SSH, XML, Modbus TCP (Sunspec)

Monitoring

Web user interface (WUI)

Integrated

Local monitoring

Wirelessly allowed via any Wi-Fi ® device connecting the integrated WUI or running Plant Viewer for 

Mobile

Remote monitoring

Plant Portfolio Manager ® / Plant Viewer™ / Plant Viewer for mobile

Data Logging Specifications

Data sampling rate

High frequency data sampling (less than 1 minute average)

Local data storage

Log data for 30 days based on 15-minute intervals

Upgradeability

Remotely via Aurora Vision® Plant Management Platform / locally via integrated Web User Interface 

(1)

Advanced functionalities

Remote O&M operations

Inverter’s parameter setting 

(2)

 / inverter’s firmware upgrade 

(2)

Smart grid functionalities

Grid control power-management enabled 

(2)

Power Supply

DC power consumption

~ 2W

Environmental Parameters

Ambient temperature range

[-20; +85]°C

Environmental protection

IP 20

Relative humidity

<85% Non-condensing

Mechanical Parameters (per unit)

Dimensions (H x W x D)

 97mm x 46mm x 16mm (3.81’ x 1.81’ x 0.63’)

Weight

0.06 lbs (26g)

Mounting system

Inverter’s expansion slot

Compliance

Marking

CE / RCM / Wi-Fi Certified™

Emissions

47 CFR FCC Part 15 Subpart C, EN 55022 Conducted and radiated emission

Immunity

EN55024

1. Available from FW version FW 1.8.x

2. Check for availability

Remark. Features not specifically listed in the present datasheet are not included in the product

Summary of Contents for VSN300

Page 1: ...uide the safety and installation information provided in the product manual must be read and followed The technical documentation for the product is available at the website The device must be used in the manner described in the manual If this is not the case the safety devices guaranteed by the inverter might be ineffective ...

Page 2: ... help 3 RF Exposure This device complies with Part 2 1091 of the FCC Rules for an uncontrolled environment This equipment should be installed and operated with a minimum distance of 20cm between the antenna and the user Refer to the specific section describing procedures how to integrate and use this device into the host fixed mount inverter Changes or modifications made to this equipment not expr...

Page 3: ...OGGER CARD and router can be increased in different ways 1 Change the direction of the antenna 2 Find a new location for the router taking care about the signal decrease due to materials through which the radio signal has to pass Before mounting the system it is important to consider the possible scenarios see below and evaluate the right position for Wi Fi router 1 2 NO OK Distance less less than...

Page 4: ...rvice cable glands of the inverter using a 25mm wrench Pass the antenna connection cable into the inverter by passing it through the M20 cable gland opening the gasket the plastic lock nut and the adapter If used Attach the antenna bulk head connector to the inverter using the supplied plastic lock nut torque 5N m For some inverter models UNO 2 0 2 5 I OUTD and TRIO 5 8 7 5 8 5 TL OUTD it will be ...

Page 5: ...U11 U7 J2 1 2 23 24 J1 U8 U3 U11 U7 J2 1 2 23 24 2 3 U7 J2 U7 J2 2 3 Special note for installation on inverter equipped with arc fault device In these type of inverter is necessary to install a standoff supplied with the equipment under the mechanical mounting bracket J1 U8 U3 U11 U7 J2 1 2 23 24 J1 U8 U3 U11 U7 J2 1 2 23 24 Installation with arc fault connection board At the end of installation p...

Page 6: ...t browser 4 Insert all the information required by the configuration wizard 4a Select the language 4a 4b Verify that the time zone of the installation site is correct or insert if it is missing 4b 4c The VSN300 is able to operate in two different modes of operation AP mode access point in this mode is enabled local monitoring only The card behaves like an access point generating a wireless network...

Page 7: ...Plant Portfolio Manager Plant Viewer Plant Viewer for mobile Data Logging Specifications Data sampling rate High frequency data sampling less than 1 minute average Local data storage Log data for 30 days based on 15 minute intervals Upgradeability Remotely via Aurora Vision Plant Management Platform locally via integrated Web User Interface 1 Advanced functionalities Remote O M operations Inverter...

Page 8: ...purchase orders the agreed particulars shall prevail FIMER does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior ...

Reviews: