Parameter number 266: 

Protocol type COM2 

 

Menu: 

Communication 

Short description 

PA2 = MZ 

Default setting: 

 

Set the value of P266 to 7 for GSM modem configuration 

 
Both the internal modem option card and an external modem connected by means of connector X4 
use port COM2 in the inverter itself. 
 
N.B. 
The inverter must be completely switched off and switched on again when setting the modem 
for the first time. 
After  switching  on  the  electronics  of  the  inverter,  it  takes  approx.  80  seconds  before  the 
modem is initialised. The modem is ready to receive after a period of roughly 2 minutes. 
 
If you have to set the PIN number of the SIM card you have to modify the content of the parameter 
number P282 (SIM card PIN number): 
 

Parameter number 282: 

SIM Card PIN number 

 

Menu: 

Communication 

Short description 

PIN 

Default setting: 

0  

 

Enter your PIN number here (Not necessary if you have a SIM Card without pin) 

 

 

After finishing setting the parameters, de-energise the inverter. 

 

Carefully insert the SIM card (as soon as there is no voltage). 
Internal card: (– Gold contacts pointing towards cover of the inverter) 

 (– Canted edge must still be easy to read when the card in inserted) 

Note: The exact position is a bit difficult to find, so you will have to gently “waggle” the 
card to find the position in which it can be inserted by  exerting just a slight amount of 
pressure. Please make sure you don't let go of the card and allow it fall into the modem, 
and  ensure  it  is  fully  inserted.  When  properly  inserted,  the  card  protrudes  about  1  mm 
out of the modem. 

External box: ( Contact surface is not aerial connector) 

 

You  can  now  switch  the  inverter  on  again.  Check  the  status  of  the  modem,  see  chapter  9, 
"Fault Analysis", "Initialisation completed": "21007" 

N.B. 
The inverter must be completely switched off and switched on again when parameterising the 
modem for the first time. 
After  switching  on  the  electronics  of  the  inverter,  it  takes  approx.  80  seconds  before  the 
modem is initialised. The modem is ready to receive after a period of roughly 2 minutes. 

User Interface 

The user interface we have developed and provide is called FIMERNet. 
 
You  may,  of  course,  also  use  the  computer  communications  software  that  goes  by  the  name 
Hyperterminal. 
 
 

Summary of Contents for R25 Series

Page 1: ...d PV Inverter series R25 Grid connected PV Inverter series R25 Grid connected PV Inverter series R25 Grid connected PV Inverter series R25 R55 R55 R55 R55 InternalandexternalGSMmodemuserguideforsingle phaseinverter ...

Page 2: ......

Page 3: ...f it as a whole or in part in forbidden unless expressly authorised The contents pictures and texts can be use for training the installers and the end users of the product This manual cannot be used any other scope different from the user instruction necessary to install control and run the solar inverter While every care has been taken during the preparation the compilation and checking to ensure...

Page 4: ...us integrated communications options mean that our inverter is easy to maintain and operate Along side the usual RS232 and RS485 interfaces there is also an Ethernet interface The d integrated 4 line display offers a wide range of possibilities for communication and data transfer The following documentation provides installation instructions for the inverter Please observe at all times the safety ...

Page 5: ...ces of technical equipment Accessories necessary for installing the GSM modem The solar inverters made by FIMER can be controlled parameterised and monitored by means of a GSM modem To this end you either have to connect an external modem to the 25 pin Sub D connector on the inverter or install the corresponding option card in the inverter itself The accessories and device necessary to connect the...

Page 6: ...not be retrofitted because the sealing material could become damaged by such a measure In that case please keep in contact with Fimer Inverters that conform to degree of protection IP 21 must be retrofitted by specially trained personnel only Caution When carrying out such work remember you are dealing with a piece of equipment that carries high voltage levels Furthermore always observe the releva...

Page 7: ... the ribbon cable to the relevant connector on the microprocessor card Do not yet secure the option card rather leave it protruding relatively far out of the opening slot place Photo Pushing the option card with ribbon cable onto the microprocessor card but not yet fully inserting it 6 Reconnect the ribbon cable from the cover to the microprocessor card 7 Please make absolutely sure that the two c...

Page 8: ... to a 230 V AC 50 Hz power supply system When the adapter is plugged into the power supply the red LED indicator on the top side of the enclosure must come one and remain lit A low voltage ELV connector must be plugged into the connection socket at the cable termination This low voltage connector has an outer diameter of 5 0 mm and an inner diameter of 2 1 mm The polarity marking inner pole outer ...

Page 9: ...ing the parameters de energise the inverter Carefully insert the SIM card as soon as there is no voltage Internal card Gold contacts pointing towards cover of the inverter Canted edge must still be easy to read when the card in inserted Note The exact position is a bit difficult to find so you will have to gently waggle the card to find the position in which it can be inserted by exerting just a s...

Page 10: ...ndicates the protocol type currently active 0 ASCII Protocol HyperTerm without modem 1 FIMER Protocol FIMERNet without modem 3 Modem with ASCII protocol 4 Modem with FIMER protocol FIMERNet with modem 7 GSM Modem FIMERNet with GSM modem Note Set the value of P266 Protocol type COM2 for GSM modem configuration Examples MZ 20137 The decimal place that indicates the initialisation status is slowly in...

Page 11: ... be initialised Following initial installation switch the unit off and on again Initialisation of the modem commences after approx 80 seconds but is only completed after approx 2 minutes If without there being a call the message number 21007 appears on the inverter display next to parameter 162 the modem is either not connected to the inverter or it can not be initialised Check the modem its power...

Page 12: ...______________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ _____________________________________________________...

Page 13: ..._______________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ____________________________________________________...

Page 14: ...______________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ _____________________________________________________...

Page 15: ...________________________________________________________________________________ ________________________________________________________________________________ 13 ...

Page 16: ..._____________________________________________________________________________14 Cod 910 400 119 REV00 ...

Reviews: