65
000868BG -F
5 - Installation
• Give each wire a pull test to confirm the connection is secure
• In the AC filter board
40
set the switch (S1) based on the configuration
of the output connections:
-
3WIRES
position. Three wires configuration (R+S+T)
-
4WIRES
position. Four wires configuration (R+S+T+Neutral)
• Once connection to the AC output screw terminal block
38
has been
completed, retighten (10.0 Nm torque) the cable gland firmly and check
seal.
40