Filtration Group Air System Products Robo-Drain RD11-VAC Installation & Operation Manual Download Page 4

 

4

 

The Robo-Vac is designed for trouble-free operation.  When 
installed and operated properly, the Robo-Vac will provide 
years  of  reliable  service  collecting  and  discharging 
condensate, along with pipe scale and other contaminants 
typically found in vacuum systems. 

 

INSTALLATION 

 

 

Before  installing  the  drain,  ensure  the  source  vessel  is 
isolated from the interconnecting piping to the drain. 
 
Confirm the air system pressure will not exceed the 90 PSI 
(6.2 bar) rating of the drain and the inlet temperature should 
not exceed 180 

o

F (82 

o

C). 

 
The condensate source must be connected to the ¾” NPT 
inlet connection on the pinch valve. The installation of a pre-
strainer is not required or recommended. 
 
Install the drain on a level surface and as close to the source 
to be drained as possible. Since the Robo-Vac uses gravity 
to fill the reservoir, the entire drain must be installed below 
the source. It isn’t recommended that flexible tubing be used 
on the discharge to prevent it from whipping casing damage 
or injury. 
 
If the drain is to be installed where the temperatures can fall 
below 32

o

F (0 

o

C), special precautions are needed, including 

but  not  limited  to  heat  tracing  pipelines  and  the  optional 
immersion heater. 
 
The  Robo-Vac  will  only  accept  condensate  via  the  pinch 
valve  connected  to  the  upper  drain  inlet  connection.    The 
lower  inlet  connection  has  been  permanently  sealed  to 
prevent inadvertent use. 
 
The  use  of  isolation  valves  and  bypass  piping  will  permit 
quick and easy routine maintenance.  
 
The Robo-Vac uses compressed air to drive (control) a drain 
cycle. 

ONLY  CLEAN  DRY  AIR  MUST  BE  USED!

  The 

required  control  air  pressure  for  the  standard  models, 
irrespective  of  system  pressure  is    60-130  PSIG  (4.1-9.0 
barg). The Robo-Vac can be supplied as an LP variant and 
will model should be between 40 and 130 PSIG (2.8 and 9.0 
barg).The Robo-Vac is supplied with a filter for installation 
on the control head. The use of unfiltered air can result in 
failure and can void the product warranty. 
 
Once installed and control air supplied, the drain is ready to 
be placed in service. 

 
 
CHECKING THE OPERATION 

After installation is complete and the drain is in service, a 
check should be made that the drain is functioning properly.  
1.  Ensure  that  condensate  is  properly  entering  the 

reservoir.  This  can  be  easily  done  looking  through  the 
translucent reservoir 

2.  Press the test button to ensure the drain valve opens and 

closes when the button is released. 

3.  Inspect  for  any  air  or  condensate  leaks.  Correct  as 

necessary.  

 
 

TROUBLESHOOTING

 

If condensation is not entering the reservoir, check for the 
following: 

1. 

Check that any valves between the source and drain are 
open. 

 
If the drain is not emptying: 
1.  Press the test button to force a manual drain cycle.  If the 

air  actuator  does  not  open  the  valve  ,  check  that  the 
control  air  supply  is  at  least  the  minimum  pressure 
required. 

2.  If the valve opens, but the drain does not empty quickly, 

no more than 20 seconds, ensure that there is system 
pressure. 

3.  If still not emptying, check the downstream piping from 

the drain valve to ensure there isn’t a closed valve or an 
obstruction. 

4.  If  the  drain  is  still  not  draining,  suggest  contacting  the 

factory. 
 

OPTIONS 

High Level Alarm 
Mechanical Cycle Counter 
Digital Cycle Counter 

  

 

 

Summary of Contents for Air System Products Robo-Drain RD11-VAC

Page 1: ...Condensate Drain Model RD11 VAC AIR SYSTEM PRODUCTS 51 Beach Ave Lancaster NY 14086 716 683 0435 ASPSalesTeam airsyspro com www airsyspro com Installation Operation Manual Making the World Safer Healt...

Page 2: ...INSTALLATION 4 POST INSTALLATION CHECK 4 TROUBLESHOOTING 4 OPTIONS 4 INSTALLATION CONSIDERATIONS 5 RECEIVER 5 FILTER AND AFTERCOOLER SEPARATOR 5 REFRIGERATED DRYER 5 INTERCOOLERS 5 BALANCE LINE 5 GENE...

Page 3: ...erly enter the Robo Vac reservoir the condensate line to the Robo Vac must always be installed below the source to be drained It is equally important to provide a means such as a balance line for the...

Page 4: ...d air to drive control a drain cycle ONLY CLEAN DRY AIR MUST BE USED The required control air pressure for the standard models irrespective of system pressure is 60 130 PSIG 4 1 9 0 barg The Robo Vac...

Page 5: ...pipeline and as close to the cyclone separator as possible REFRIGERATED DRYER If a balance line is required it must be connected to the port located on top of the separator that is closest to the dis...

Page 6: ...ing on application MATERIALS Reservoir Aluminum and Composite Stainless Steel and Nickel plated Optional Drain Valve Bronze w SS Ball and Stem Full SS Optional Trigger Float Stainless Steel Trigger Se...

Page 7: ...7...

Page 8: ...8...

Page 9: ...tight 5 On the standard Robo Vac with the translucent vessel if the condensate level isn t visible due to vessel coated with contamination it is recommended to remove the drain from service and follow...

Page 10: ...All design specifications subject to change without notice 2021 ASP S RD 4VAC 020921 AIR SYSTEM PRODUCTS 51 Beach Avenue Lancaster NY USA P 1 716 683 0435 www airsyspro com...

Reviews: