ILV660-001
Instrucciones de uso
1.
Descripción
1.1 Indicaciones para su aplicación
The vibrating level indicator ILV-660 is to be used to control the
maximum or minimum level of bulk solids in silos or vessels.
It is recommended for dusty and powdery, granulated and grainy
bulk goods like dust, flour, grain, sand, plastic, etc.
1.2
Funcionamiento
The probe must to be exposed to the material. The probe of these
controllers is activated to its resonant frequency by a piezoelectric
system. When the product covers the probe, the vibration is
dampened and the control unit reverses the signal.
When the product disappears from the fork, it returns to the normal
vibrating state and the signal turns to the initial position.
The device has a insensitive rod between the probe and the
proccess connection to avoid the possibility of settle of the product
over the probe up to 75 mm.
1.3
Technical data
Manufacturer
Talleres Filsa, S.A.U.
Address
Bernat Metge, 33
08100 Mollet del Vallès
(Barcelona)
Name
Vibrating level indicator
Type
ILV-660
ref:
2190-0-600
Supply voltage
24 V DC ± 10 %
1 W
3
Density of the product
From 0.05 t/m
Maximum pressure
+10 bar
Cable entry
DIN43650 connector
Detecting level
1 s
Starting vibrating
2 ... 5 s
Weight
0.73 kg
Max. load upon the probe
80 N
1.4
Materials
Housing and probe
Stainless Steel 1.4301
with a minimum
3
bulk density from 0.05 t/m and a maximum grain size of 10 mm.
It is not recommended for sticky solids or products that have the
tendency to settle over the fork.
Power consumption
Response time
Product temperature
-20 °C ... +70 °C
Ambient temperature
-20 °C ... +60 °C
Transistor output
PNP or NPN depending on the
connection
Function status
Relay enabled: red LED
Resonance frecuency
460 Hz
Protection
IP65 according DIN EN60529
350 mA / 24 V DC
1.5
Dimensions
Approximate measures are given in mm.
-
-
-
2.
Installation
2.1 Preparing for use
The probe must not be hit by the filling stream. To avoid this,
deflect the filling stream or install a deflection screen or a
protection roof. It is also recommended to install a protection roof
when the controllers are used as empty-indicator or medium-
indicator in silos where vaults could be formed or where high
loads above it could exist.
For a proper function, the device should be installed with a 20 º to
30 º slope from the horizontal onto the silo wall to to facilitate the
flow of the material and to prevent the material from remaining
over the probe.
Read the Safety instructions and the Operating instructions before
using the controller.
ILV-660
Talleres Filsa, S.A.U.
www.filsa.es
•
•
•
•
•
E-08100 Mollet del Vallès (Barcelona)
Tel.
+34 93 570 46 01
Fax
+34 93 570 24 71 [email protected]
03
10/15
MI-ILV660-EN-03
© by FILSA
Probe
LED
137
Ø 40
340
157
82
Ø 6.5
36
1 " tappered
DIN 2999
Weather protection
Protection roof
ILV660-002