INSTALLATION

3

OPERATING INSTRUCTIONS

CALIBRATION

305 remote dispensers and tank top pumps must be installed

in accordance with the applicable requirements of the Automo-

tive and Marine Service Station Code, NFPA No. 30A, and the

National Electrical Code, NFPA No. 70.  They are designed for

use either inside of outside of buildings subject to the accep-

tance of inspection authorities having jurisdiction at points of

installation.

Mechanical Installation

1. Mount pump securely on top of tank (see pump mounting

instructions included with pump).

2. Refer to mounting plate tank mounting diagram, if appli-

cable, and install mounting plate to tank (position plate for

desired dispenser height and to allow for most direct piping

from pump to dispenser).

3. Place dispenser on mounting plate. 

 NOTE:

  The screw heads

will protrude through the mounting plate clearance holes.

Remove four 1/2" hex head screws at dispenser inlet one or

two at a time to prevent movement of internal components

of dispenser.  Place 5/16" or larger flat washer on screw and

4. Carefully measure and install piping between pump with

union located at pump.  Pipe is not intended to support pump

or dispenser in any manner.

Electrical Installation

Refer to installation and wiring diagrams for pump and

dispenser conduit connection locations and wiring method.

1. Remove dispenser cabinet top and junction box cover (see

“ASSEMBLY/DISASSEMBLY” section in this manual).

2. If using conduit opening on left end of junction box, remove

plug and install a 3/4" x 1/2" conduit reducer bushing and a

1/2" short conduit elbow.  Elbow should line up with hole in

dispenser base.  Run rigid conduit from pump motor junction

box to opening in base.  Suggest using 1/2" expansion unions

for ease of assembly.

3. Run 1/2" rigid conduit from power source to remaining

opening in base.

4. With power turned off, connect pump wires and power wires

to line switch leads per wiring diagram.  Connect ground

wires to ground screws in junction boxes and to ground

source.

1. After hose, nozzle, filter, etc. have been installed, hold nozzle

open into tank opening or container and turn on switch

handle.  Allow pump to prime and evacuate air from system.

2. Reset meter to zero.

3. To check meter calibration, insert nozzle into container of

known volume and fill.  If calibration is required, do so before

replacing cabinet top.

Locking Mechanism

Models with universal nozzle boots:

The nozzle retainer is designed to accept a padlock for

locking the nozzle in place when the device is not in use.

Padlock not supplied.

Models with standard nozzle boots:

The handle stop is provided with an elongated hole to

accept a padlock for locking the nozzle in place when the

device is not in use.  A padlock with a minimum shackle

height of 2" and a maximum height of 3" is required.  Padlock

is not supplied.

The Fill-Rite Series 900 Meter used inside the 305 pumping

system is calibrated at the factory for metering gasoline in

either U.S. gallons or liters, depending on the model.  Calibra-

tion is recommended upon initial use, and required after

disassembly, when metering a different fluid, or after signifi-

cant wear. Calibration must be done between 6 and 40 GPM.

Meter calibration can be easily changed by following the

calibration procedure listed below.  A proving container or a

container of KNOWN volume will be needed for the calibration

procedure.  The container’s volume should be at least five

times larger than the unit of calibration.  For example, a five

gallon container should be used when calibrating for gallons.

Procedure for Calibration:

1. Fill container to a known volume.

2. If meter amount is incorrect, turn calibration screw (item 37)

counterclockwise for more liquid or clockwise for less liquid.

3. Repeat step 1 and 2 until calibration is acceptable.

Summary of Contents for 305RU

Page 1: ...305 REMOTE DISPENSER Owner s Operation Safety Manual OUTSTANDING FEATURES From 6 to 40 GPM 23 to151 LPM Meter accuracy of 2 Model 305RU ...

Page 2: ...ositive displacement nutating disc type Can be calibrated for 2 accuracy within a fluid range of 6 to 40 GPM 23 to 151 LPM Register Three resettable unit wheels with large 11 16 figures and tenths wheel Totalizer reads to 999 999 9 gallons Cabinet measures 13 W x 11 1 2 D x 10 1 2 H Liter measure Four resettable unit wheels Totalizer reads to 99 999 999 liters Front or rear discharge Red or white ...

Page 3: ...r source to remaining opening in base 4 Withpowerturnedoff connectpumpwiresandpowerwires to line switch leads per wiring diagram Connect ground wires to ground screws in junction boxes and to ground source 1 Afterhose nozzle filter etc havebeeninstalled holdnozzle open into tank opening or container and turn on switch handle Allowpumptoprimeandevacuateairfromsystem 2 Reset meter to zero 3 To check...

Page 4: ...k of meter 2 Meterchamberassemblycanberemovedbyremovingfour screws item 5 3 Reassemble by reversing procedure Meter chamber assembly consists of upper and lower chambers and nutating disc If replacement of any components of the meter chamber assembly is required the complete assembly must be replaced due to the precise method of its construction This assures a proper fit and a correctly operating ...

Page 5: ... 5RG 1XW RWWHU 3LQ 6 6ZLWFK HYHU URRYH 3LQ 6ZLWFK DQGOH UDFNHW 2XWOHW LWWLQJ 6 6ZLWFK 5RG LWFK 3LQ OLS 6ZLWFK HYHU QFOXFHG Z WHP RFNQXW QFOXGHG Z WHP 6 6WDQGDUG 1R OH RRW 5HG 6WDQGDUG 1R OH RRW KLWH 2SW 1LSSOH RQGXLW OERZ RQGXLW 1LSSOH 8 1XW 0 RQGXLW OERZ DVKHU 2 6 H 3OXJ 6ZLWFK RXVLQJ UDFNHW 6ZLWFK RXVLQJ VVHPEO 0HWHU 8 6 DOORQ 0HWHU LWHU 2SW DWKH XW DVNHW QOHW DVWLQJ 5HVHW RXSOLQJ 6HW 6FUHZ 5HVH...

Page 6: ...6 WHEN ORDERING REPAIR PARTS BE SURE TO GIVE RE PLACEMENT PART NUMBER DATE OF MANUFACTURE AND DISPENSER SERIES NUMBER THIS WILL ENSURE THAT THE CORRECT REPLACEMENT PART IS SUPPLIED ...

Page 7: ...WIRING DIAGRAM TANK MOUNTING LAYOUT DISPENSER BASE LAYOUT 7 ...

Page 8: ...19 800 16 F3820 Shaft Cluster Gear 1 20 800 159 F3841 Cluster Gear U S Gallon 1 800 161 F3843 Cluster Gear Liter Opt 21 800 18 F3830 Washer 1 22 900 11 F8063 Driver Pinion Shaft Included w item 7 1 23 900 13 F8065 Retaining Ring 1 24 900 12 F8064 Driver Pinion 1 25 800 55 F3980 Washer 2 900 SERIES METER PARTS LIST 900 SERIES METER PARTS LIST ITM PART PROC NO NO NO DESCRIPTION QTY 26 800 160A F3845...

Page 9: ...ean O ring seal and seat area leakage Bad seal Replace seal TROUBLESHOOTING GUIDE PROBLEM POSSIBLE CAUSE SOLUTION 9 ABOVEGROUND TANK INSTALLATION NOTE USE APPROVED PIPE COMPOUND ON ALL PIPE THREADS ELECTRICAL NOTE ELECTRICAL WIRING SHOULD BE DONE IN ACCORDANCE WITH APPROVED LOCAL ELECTRICAL CODES AND BY A LICENSED ELECTRICIAN THE PUMP SHOULD BE PROPERLY GROUNDED AND RIGID CONDUIT SHOULD BE USED WH...

Page 10: ... Corporation Manufacturer warrants to each buyer of its products the Buyer for a period of 12 months from date of installation but in no event more than 18 months from date of manufacture that goods of its manufacture Goods will be free from defects of material and workmanship Specific to Series 10 12 20 and 22 Warranty is under stood not to exceed 6 months and is specific to all related items Man...