FILL-RITE 305RU Owner'S Operation & Safety Manual Download Page 2

Dear Fill-Rite Customer,

Thank you for buying a Fill-Rite product.  We believe that you

have bought the best.  This piece of literature contains

information about your new equipment and its operating and

service requirements.  Please take a few minutes to read it

carefully.

Fill-Rite's products are distributed around the world and are

the result of people at Fill-Rite working together to design,

manufacture, sell, ship and service products which meet the

needs of each and every customer.

If, for any reason, any of our products do not meet your

performance expectations, we would like to hear from you.

Our best sales force is you, our customer, and we want you to

be satisfied.  We appreciate your purchase of a Fill-Rite

product and look forward to providing your future equipment

needs.

Sincerely,

George P. Jenkins

President

2

GENERAL DESCRIPTION

The 305 Remote Dispenser is a power operated petroleum

dispensing device, for use on fixed aboveground tanks with a

maximum capacity in accordance with NFPA 30A.  It is used

in conjunction with a tank top pump and can handle a variety

of fuels up to 40 GPM at ±2% accuracy.

The dispenser can operate with a 110V/60Hz or 220V/60Hz

pump, if desired.  The 305 is equipped with a Fill-Rite 900

Series Meter with a manual reset (for non-resale applications).

The 900 Meter is accurate at ±2% in a flow range from 6 to 40

GPM.

Design Features

•1" NPT inlet, 1" NPT outlet

•50 PSI maximum pressure

•Furnished with 12' hose and manual nozzle

•Meter:

•Positive displacement, nutating disc type

•Can be calibrated for ±2% accuracy within a fluid

range of 6 to 40 GPM (23 to 151 LPM)

•Register:

•Three resettable unit wheels with large 11/16"

figures and tenths wheel

•Totalizer reads to 999,999.9 gallons

•Cabinet measures 13"W x 11 1/2"D x 10 1/2"H

•Liter measure:

•Four resettable unit wheels

•Totalizer reads to 99,999,999 liters

•Front or rear discharge

•Red or white cabinet

•Universal nozzle boot for automatic or vapor recovery

nozzles

•Automatic nozzle for standard or universal boot

•High flow automatic nozzle for universal boot

•Filter kits

•Tank mounting bracket

Fluid Compatibility

If in doubt about compatibility of a specific fluid, contact

supplier of fluid to check for any adverse reactions to the

following wetted materials.

Steel

Polyester

Aluminum

Fluorocarbon

Buna N

300S Stainless Steel

TECHNICAL INFORMATION

OPTIONS

DANGER

Electrical wiring should be

done by a licensed electrician

in accordance with NFPA 30A

and 70.  Improper use or instal-

lation of this product can

cause serious bodily injury or

death.

1. DO NOT smoke near dispenser or use dispenser

near an open flame when pumping flammable

fluids. Fire could result. Installation should be in

accordance with NFPA 30A.

2. Dispenser should be properly grounded and rigid

conduit should be used when installing electrical

wiring.

3. Use gasoline resistant compound on threaded

joints.

4. This product should not be used for fluid transfer

into aircraft.

5. This product is not suited for use with fluids for

human consumption or fluids containing water.

6. A filter should be used on dispenser outlet to ensure

that no foreign material is transferred to fuel tank.

SAFETY INSTRUCTIONS

Summary of Contents for 305RU

Page 1: ...305 REMOTE DISPENSER Owner s Operation Safety Manual OUTSTANDING FEATURES From 6 to 40 GPM 23 to151 LPM Meter accuracy of 2 Model 305RU ...

Page 2: ...ositive displacement nutating disc type Can be calibrated for 2 accuracy within a fluid range of 6 to 40 GPM 23 to 151 LPM Register Three resettable unit wheels with large 11 16 figures and tenths wheel Totalizer reads to 999 999 9 gallons Cabinet measures 13 W x 11 1 2 D x 10 1 2 H Liter measure Four resettable unit wheels Totalizer reads to 99 999 999 liters Front or rear discharge Red or white ...

Page 3: ...r source to remaining opening in base 4 Withpowerturnedoff connectpumpwiresandpowerwires to line switch leads per wiring diagram Connect ground wires to ground screws in junction boxes and to ground source 1 Afterhose nozzle filter etc havebeeninstalled holdnozzle open into tank opening or container and turn on switch handle Allowpumptoprimeandevacuateairfromsystem 2 Reset meter to zero 3 To check...

Page 4: ...k of meter 2 Meterchamberassemblycanberemovedbyremovingfour screws item 5 3 Reassemble by reversing procedure Meter chamber assembly consists of upper and lower chambers and nutating disc If replacement of any components of the meter chamber assembly is required the complete assembly must be replaced due to the precise method of its construction This assures a proper fit and a correctly operating ...

Page 5: ... 5RG 1XW RWWHU 3LQ 6 6ZLWFK HYHU URRYH 3LQ 6ZLWFK DQGOH UDFNHW 2XWOHW LWWLQJ 6 6ZLWFK 5RG LWFK 3LQ OLS 6ZLWFK HYHU QFOXFHG Z WHP RFNQXW QFOXGHG Z WHP 6 6WDQGDUG 1R OH RRW 5HG 6WDQGDUG 1R OH RRW KLWH 2SW 1LSSOH RQGXLW OERZ RQGXLW 1LSSOH 8 1XW 0 RQGXLW OERZ DVKHU 2 6 H 3OXJ 6ZLWFK RXVLQJ UDFNHW 6ZLWFK RXVLQJ VVHPEO 0HWHU 8 6 DOORQ 0HWHU LWHU 2SW DWKH XW DVNHW QOHW DVWLQJ 5HVHW RXSOLQJ 6HW 6FUHZ 5HVH...

Page 6: ...6 WHEN ORDERING REPAIR PARTS BE SURE TO GIVE RE PLACEMENT PART NUMBER DATE OF MANUFACTURE AND DISPENSER SERIES NUMBER THIS WILL ENSURE THAT THE CORRECT REPLACEMENT PART IS SUPPLIED ...

Page 7: ...WIRING DIAGRAM TANK MOUNTING LAYOUT DISPENSER BASE LAYOUT 7 ...

Page 8: ...19 800 16 F3820 Shaft Cluster Gear 1 20 800 159 F3841 Cluster Gear U S Gallon 1 800 161 F3843 Cluster Gear Liter Opt 21 800 18 F3830 Washer 1 22 900 11 F8063 Driver Pinion Shaft Included w item 7 1 23 900 13 F8065 Retaining Ring 1 24 900 12 F8064 Driver Pinion 1 25 800 55 F3980 Washer 2 900 SERIES METER PARTS LIST 900 SERIES METER PARTS LIST ITM PART PROC NO NO NO DESCRIPTION QTY 26 800 160A F3845...

Page 9: ...ean O ring seal and seat area leakage Bad seal Replace seal TROUBLESHOOTING GUIDE PROBLEM POSSIBLE CAUSE SOLUTION 9 ABOVEGROUND TANK INSTALLATION NOTE USE APPROVED PIPE COMPOUND ON ALL PIPE THREADS ELECTRICAL NOTE ELECTRICAL WIRING SHOULD BE DONE IN ACCORDANCE WITH APPROVED LOCAL ELECTRICAL CODES AND BY A LICENSED ELECTRICIAN THE PUMP SHOULD BE PROPERLY GROUNDED AND RIGID CONDUIT SHOULD BE USED WH...

Page 10: ... Corporation Manufacturer warrants to each buyer of its products the Buyer for a period of 12 months from date of installation but in no event more than 18 months from date of manufacture that goods of its manufacture Goods will be free from defects of material and workmanship Specific to Series 10 12 20 and 22 Warranty is under stood not to exceed 6 months and is specific to all related items Man...