TWINFLEX
®
pro Repeater Panel Engineering and Commissioning Manual
16
Commissioning
•
Check that the repeater has been correctly and securely mounted to the wall.
•
Check that the date and time are correct and match the date and time on the main control panel
which it is connected to. Check that the time increments with the main control panel which it is
connected.
•
Carry out all 5 tests below:
Option 3. Test RDU
1. Test LEDs
2. Test Keypad
3. Test Buzzer
4. Test LCD
5. Test Backlight
•
Verify that fire alarms and faults are displayed correctly and match the main control panel which it is
connected to.
•
Training for the users of the system and responsible persons See End User Training below.
Fault finding
If the date and time do not update and are not in synchronisation with the main panel check the wiring
at the repeater and the main panel is correct.
Check the setting in the main panel and repeater.
The panel will report RDU missing if there is no communications between the main control panel and
the repeater or if the repeater address number does not match the RDU enabled number in Option 1
PB RDU Supervise in the main control panel.
If for example RDU 1 is set in the main control panel Option 1, PB RDU Supervise and the repeater that
is connected to the peripheral bus is set to a different address i.e. number 2, the panel will report “RDU
1 Missing”.