TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
44
This active control will allow the engineer to automatically override any
delay in the zone of origin. Use the
LEFT
and
RIGHT
keys to toggle
through the following options. Once the correct option has been
selected press the
ENTER
key.
1. INSTANT – If any zone programmed with an
output delay enters an alarm
condition, the output delay on that
initiating zone will be cancelled. All
other zones will operate as per their
output delay settings.
2. SETTING – All zones will operate as per their
output delay settings.
This active control will allow the engineer to temporarily switch off the
panel buzzer whilst in engineer mode. When the user exits engineer
mode, the buzzer will be re-enabled. Use the
LEFT
and
RIGHT
keys to
toggle through the options, then press
ENTER
to confirm the change.
This active control will allow the engineer to change the code for
access to the user menus. Use the
UP
and
DOWN
keys to move the
cursor between options and the alphanumeric keypad to enter the
code. Press the
ENTER
key to confirm the change.
This active control will allow the engineer to change the code for
access to the supervisor menus. Use the
UP
and
DOWN
keys to move
the cursor between options and the alphanumeric keypad to enter the
code. Press the
ENTER
key to confirm the change.
This active control will allow the engineer to change the code for
access to the engineer menus. Use the
UP
and
DOWN
keys to move
the cursor between options and the alphanumeric keypad to enter the
code. Press the
ENTER
key to confirm the change.
8. Alarm Delay
6. Zone of Origin Delay
9. Panel Details
1. Buzzer
1. ON / OFF
9. Panel Details
2. Access Code
1. User
9. Panel Details
2. Access Code
2. Supervisor
9. Panel Details
2. Access Code
3. Engineer
01/09/09 22:26 ENGR
ORIGIN ZN : INSTANT
1.INSTANT 2.SETTING
Press <> OR Esc Key
EXISTING CODE:8737
NEW CODE
:
CONFIRM CODE
:
Press <> OR Esc Key
01/09/09 22:26 ENGR
BUZZER: OFF
1.ON 2.OFF
Press <> OR Esc Key
EXISTING CODE:7877
NEW CODE
:
CONFIRM CODE
:
Press <> OR Esc Key
EXISTING CODE:3647
NEW CODE
:
CONFIRM CODE
:
Press <> OR Esc Key
www.acornfiresecurity.com
www.acornfiresecurity.com