26-0378 Issue 5
Twinflex Hipoints can be mixed on the same zone as other types of Twinflex device (eg. Twinflex Multipoint
Detectors). The above diagram shows how to make the zone positive, zone negative and screen connections
between the control panel and Twinflex Hipoints. Refer to the instruction leaflets supplied with other Twinflex
devices for their equivalent wiring/terminal labelling details.
Please note that the cable screens should only be connected to each other (and not to the building earth) at the
Hipoints. The cable screen is connected to earth at the panel end only, via the zone “SCRN” terminal (or EARTH
terminal on the Twinflex V3 2/4/8 Zone panels).
DIL Switch Settings
The detector DIL switches may be used to program the operation of
the Hipoint Sounder. They may be altered whilst the device is still
powered or the system may be powered down completely. The last
device on the circuit must have the EOL signal enabled (switch
number 1 in the ‘ON’ position).
DIL SWITCH SETTINGS
1 2 3 4
End of line
Enabled ON
Disabled OFF
Sound Levels
High
ON
Low
OFF
Sound Patterns
Sound OFF
ON
ON
Dual Tone UK Evacuate – 800 & 970 Hz
ON
OFF
Slow Whoop Up - 500 to 1200 Hz sweep up
OFF
OFF
Dual Tone French Warble – 440 & 550 HZ
OFF
ON
Technical Data
Dimensions
. . . Width
.
. . . 120mm
Height
. . . . 128mm
Depth
. . . 100mm
Operating
temperature
. . . . . . . -10
o
C to +50
o
C
Voltage Ranges .
.
.
DC Output from Mains Powered Panel 25.5 to 35V DC
DC Output from Battery Powered Panel 20 to 26V DC
Operating
Current
. . Quiescent
. . . 345
uA
(Typical)
Sounder
High
. . . 13
mA
Sounder
Low
. . . 12
mA
Volume Level .
.
.
Sounder High .
.
.
90dB (A) @ 1m anechoic
(Dual Tone)
Loading Units (SLUs) .
.
Max per zone .
.
.
27 SLU
Sounder
High
. . . 2.5
SLU
Sounder
Low
. . . 2
SLU
Flammability
. . . . . . . . UL94-V2
IP
Rating . . . . . . . . IP
55
Part
Code
. . . . . . . . 302
0004
Technical Support
Contact your supplier for technical support on this product.
Due to the complexity and inherent importance of a life risk type system, training on this equipment is essential and
commissioning should only be carried out by competent persons. Fike cannot guarantee the operation of any
equipment unless all documented instructions are complied with, without variation. This unit complies with the EMC
directive.
Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is
reserved. Whilst every care has been taken to ensure that the contents of this document are correct at time of
publication, Fike shall be under no liability whatsoever in respect of such contents. E&OE.
SW
IT
CH OF
F
SW
IT
CH ON
1 2 3 4
O N