Fike Twinflex 802-0002 Installation And Maintenance Instructions Download Page 2

 

 

26-0352 Issue 6

 

Remember  that  the  device  at  the  end  of  the  line  must  have  its  EOL  signal  activated  using  the 
relevant EOL switch.  Do not use a resistor or capacitor (or another manufacturer’s End of Line 
device) as the end of line, as this may prevent correct operation of the zone. 

 

CONTROL PANEL

Z

O

N

E

 +

V

E

Z

O

N

E

 -

V

E

S

C

R

E

E

N

Z

  

+

Z

 -

S

C

R

E

E

N

TWIN FLEX

INPUT MODU LE

Z

 +

Z

 -

S

C

R

E

E

N

TWIN FLEX

INPUT MODU LE

Note: the scre en connection at each Input Module i s via a separate terminal

connector (not inclu ded) an d is not on  the circuit b oard.

 

 
Twinflex Input Modules can be mixed on the same zone as other types of Twinflex device (eg. Twinflex Multipoint 
Detectors).  The  above  diagram  shows  how  to  make  the  zone  positive,  zone  negative  and  screen  connections 
between the control panel and Twinflex Input Modules. Refer to the instruction leaflets supplied with other Twinflex 
devices for their equivalent wiring/terminal labelling details. 
 
Please note that the screen connections at each Input Module should only be connected to the zone cable screen 
and NOT to the building earth. The cable screen is connected to earth at the panel end only, via the zone “SCRN” 
terminal (or EARTH terminal on the Twinflex V3 2/4/8 Zone panels). 

 
 

Testing 

 
The unit may be tested by applying a short-circuit between the two alarm terminals, but it is better to operate the 
device which controls the contacts to which it is connected. This will cause the control panel to enter the fire state. 
When the cause for the alarm is removed the control panel may be silenced and reset. 

 
 

DIL Switch Settings 

 
The  last  device  on  the  circuit  must  have  the  EOL  signal  enabled 
(switch number 1 in the ‘ON’ position). 

 

 

 

DIL SWITCH 

SETTINGS 

 

 

End of line 

Enabled 

ON 

 

Disabled 

OFF 

 
 

S

W

IT

C

H

 O

F

F

 

S

W

IT

C

H

 O

N

 

1            

O  N

 

Summary of Contents for Twinflex 802-0002

Page 1: ...stallation 1st Fix Fix the interface surface boxed single gang in a suitable position remembering to allow enough space for the correct termination of the appropriate cables The interface PCB must be mounted within 15cm of the contacts to be monitored Installation 2nd Fix Once all testing has been carried out on the cabling and continuity integrity of the zone pair has been proven the interface un...

Page 2: ...flex Input Modules Refer to the instruction leaflets supplied with other Twinflex devices for their equivalent wiring terminal labelling details Please note that the screen connections at each Input Module should only be connected to the zone cable screen and NOT to the building earth The cable screen is connected to earth at the panel end only via the zone SCRN terminal or EARTH terminal on the T...

Page 3: ...t Quiescent 834 uA Typical End of line ON if applicable 129 uA Typical in addition to Quiescent Alarm Activated IP Module Detector 20 mA Alarm Activated IP Module Call Point 16 mA Loading Units V3 Panel Pro Panel Max Loading Units per zone 27 SLU 160 DLU IP Module Detector 3 5 SLU 20 0 DLU IP Module Call Point 3 0 SLU 16 0 DLU Flammability UL94 V2 IP Rating IP 21C Part Code Twinflex IP Module Dete...

Page 4: ...competent persons Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with without variation Fike s policy is one of continual improvement and the right to change a specification at any time without notice is reserved Whilst every care has been taken to ensure that the contents of this document are correct at time of publication Fike shall be under ...

Reviews: