background image

INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 
802-0002 Twinflex Input Module (Detector) 
802-0003 Twinflex Input Module (Call Point) 

 

 

26-0352 Issue 6

 

 

General Description  

 
The Twinflex Input module is available to enable the Twinflex system to receive a fire input signal from the  zone 
circuit. This device is compatible with the Twinflex range of Fire Alarm equipment as an auxiliary input unit. The unit 
consists  of  a  boxed  module  which  may  be  mounted  within  the  unit  to  be  monitored.  Upon  activation  the  module 
generates  a  ‘DETECTOR  ALARM’  or  ‘MANUAL  CALL  POINT  ALARM’  at  the  control  panel  depending  on 
speification. 

 

 
Device Installation 

 

All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 2002 as well as any 
special recommendations documented in the control panel installation manual. The cabling used should be of a 2-
core 1.5mm

2

 screened, fire resistant type (e.g. MICC or FP200 equivalent), and is to be wired in the form of a 

screened 2-core radial circuit (with no spurs) from the control panel, terminating at the last (“End of Line”) device.   

 
Installation 1

st

 Fix 

Fix  the  interface  (surface/boxed  single  gang)  in  a  suitable  position  remembering  to  allow  enough  space  for  the 
correct termination of the appropriate cables. The interface PCB must be mounted within 15cm of the contacts to 
be monitored. 

 

Installation 2

nd

 Fix 

Once all testing has been carried out on the cabling, and ‘continuity & integrity’ of the zone pair has been proven, 
the interface unit may be connected and commissioned. Remember to set the end of line (EOL) switch to the on 
position if the unit is the last device on the circuit. It is important to note also, that this input is a ‘latching fire input’, 
and 

is not

 fault monitored. 

 

I/P    I/P

Z+    Z -

ON

EOL  SWITCH

 

 

 

 

 

 

 

 

 

 

 

Connections 
 

The cabling should be 2-core 1.5mm

2

 screened/earthed and fire resistant e.g. MICC or FP200 equivalent type and 

is to be in the form of a 2-core radial circuit terminating at the End of Line device.  
 
No  screen  connection  is  allowed  for  within  the  device.  Incoming  and  outgoing  cable  screens  must  therefore  be 
connected through using a suitable connector. It is important to maintain the screen continuity  in order to protect 
against data corruption from interference. 

 

 

Requires Normally-Open 
contacts, closing in the 
alarm condition. 
 
Mount unit near contact 
(15cm max cable length 
from module) 

Summary of Contents for Twinflex 802-0002

Page 1: ...stallation 1st Fix Fix the interface surface boxed single gang in a suitable position remembering to allow enough space for the correct termination of the appropriate cables The interface PCB must be mounted within 15cm of the contacts to be monitored Installation 2nd Fix Once all testing has been carried out on the cabling and continuity integrity of the zone pair has been proven the interface un...

Page 2: ...flex Input Modules Refer to the instruction leaflets supplied with other Twinflex devices for their equivalent wiring terminal labelling details Please note that the screen connections at each Input Module should only be connected to the zone cable screen and NOT to the building earth The cable screen is connected to earth at the panel end only via the zone SCRN terminal or EARTH terminal on the T...

Page 3: ...t Quiescent 834 uA Typical End of line ON if applicable 129 uA Typical in addition to Quiescent Alarm Activated IP Module Detector 20 mA Alarm Activated IP Module Call Point 16 mA Loading Units V3 Panel Pro Panel Max Loading Units per zone 27 SLU 160 DLU IP Module Detector 3 5 SLU 20 0 DLU IP Module Call Point 3 0 SLU 16 0 DLU Flammability UL94 V2 IP Rating IP 21C Part Code Twinflex IP Module Dete...

Page 4: ...competent persons Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with without variation Fike s policy is one of continual improvement and the right to change a specification at any time without notice is reserved Whilst every care has been taken to ensure that the contents of this document are correct at time of publication Fike shall be under ...

Reviews: