background image

 

Page

 

4

 

of

 

7

 

ISO

 

9001:2015

 

Certified

 

Doc.

 

No.

 

06

916

 ●

 

Rev.

 

1

 

 

4.

 

The

 

detector’s

 

default

 

configuration

 

settings

 

will

 

be

 

shown,

 

including

 

the

 

detector’s

 

Model

 

and

 

Serial

 

ID.

 

If

 

the

 

detector

 

is

 

connected

 

to

 

an

 

IP

 

network,

 

the

 

assigned

 

IP

 

address

 

of

 

the

 

detector

 

will

 

also

 

be

 

displayed

 

(Refer

 

to

 

Camera

 

Configuration

 

for

 

further

 

details).

 

From

 

this

 

screen,

 

you

 

can

 

adjust

 

the

 

detector

 

settings

 

as

 

required

 

to

 

meet

 

the

 

specific

 

installation

 

requirements.

 

Refer

 

to

 

the

 

associated

 

detector

 

User

 

Manual

 

for

 

a

 

detailed

 

description

 

of

 

each

 

configuration

 

setting.

 

 

Figure

 

5:

 

FGD

 

Communicator

 

detector

 

configuration

 

screen

 

Table

 

3:

 

Detector

 

configuration

 

options

 

Function

 

Options

 

Default

 

Setting

 

Sensitivity

 

Low,

 

Medium,

 

High,

 

Extreme

 

Medium

 

Ultra

fast

 

detection

 

Disabled,

 

Enabled

 

Disabled

 

Alarm

 

Delay

 

0,

 

5,

 

10,

 

20

 

or

 

30

 

seconds

 

0

 

seconds

 

(no

 

delay)

 

Alarm

 

Latch

 

Disabled,

 

Enabled

 

Disabled

 

Window

 

Heater

 

Disabled,

 

Enabled

 

Enabled

 

Modbus

 

address

 

1

 

 

247

 

1

 

Manual

 

BIT

 

 

Alarm

 

Output

 

Test

 

Disabled,

 

Enabled

 

Disabled

 

Note:

 

Medium

 

sensitivity

 

setting

 

allows

 

detection

 

of

 

a

 

1x1ft

2

 

(0.1m

2

)

 

N

heptane

 

pan

 

fire

 

at

 

a

 

distance

 

of

 

100ft

 

(30m).

 

See

 

the

 

detector

 

specification

 

sheet

 

for

 

more

 

information.

 

 

 

Summary of Contents for FIK-IR3

Page 1: ...test version of the Communicator software Contact Fike at 1 800 979 3453 for the password 3 Detector Connections Connections to the flame detector for configuration and setup will vary depending upon...

Page 2: ...tion Ground Ground earth Connected to a screw on the housing exterior 1 24 VDC Power supply 18 32 VDC 2 24 VDC Power supply return 0 VDC 3 0 20mA in 0 20 mA analog current ouput 4 0 20mA out 5 Fault R...

Page 3: ...et RX 19 Ethernet RX 20 Shield Permanent connection to detector housing internal ground Note Highlighted pins indicate required connections 6 Detector Configuration The RS 485 connection from the flam...

Page 4: ...User Manual for a detailed description of each configuration setting Figure 5 FGD Communicator detector configuration screen Table 3 Detector configuration options Function Options Default Setting Sen...

Page 5: ...address can even change while it is still connected 1 If a static IP address is required connected to the detector and open the Communicator software Locate the Ethernet IP address of the connected de...

Page 6: ...soft or hard reset is used it will default the camera settings to factory defaults Reboot simply restarts the camera Change the camera s time The time will be displayed on the camera s video feed Ass...

Page 7: ...d the 0 20mA signal will be sent If the lens is cleaned within 20 minutes the fault relay will open and the 0 20mA signal will return to normal The options in the Main and Secondary stream groups allo...