BEFORE INSTALLING

If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 
Disconnect the power to the control panel before installing the modules. This 
system contains static sensitive components. Always ground yourself with a 
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably 
grounded.

NOTICE:

 This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The FIK-IM-10 Ten Input Monitor Module is intended for use in an intelligent 
alarm system. Each monitor module is intended to interface between a control 
panel and normally open contact devices, such as pull stations. A common 
SLC input is used for all modules, and the initiating device loops share a 
common supervisory supply and ground. Otherwise, each monitor operates 
independently from the others. Each module has its own unique address.

A pair of rotary code switches is used to set the address of the first mod-
ule from 01 to 150 (01 to 90 on panels that support up to 99 addresses). 
The remaining modules are automatically assigned to the next nine higher 
addresses. Provisions are included for disabling a maximum of two unused 
modules to release the addresses to be used elsewhere. Each module also has 
panel controlled green LED indicators. The panel can cause the LEDs to blink, 
latch on, or latch off.

C0202-00

SHIPPED ON BOARD:

(1)  Shunt in Class A/B position
 

(Shipped in Class B position, remove shunt for Class A)

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Fike system control panel. 

COMPONENTS

The following is a description of the FIK-IM-10 mounting framework:

•  One or two FIK-IM-10 modules can be installed in an FIK-BB-2 cabinet.

The FIK-BB-2 cabinet has a built-in chassis that will accommodate one or two 
FIK-IM-10 modules.

The front FIK-IM-10 module positions of each chassis are offset below the rear 

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

10

11

12

13

14

15

BASE 

ADDRESS

ADDRESS

DISABLE

NONE

ONE

TWO

THREE

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

BASE 

ADDRESS

ADDRESS

DISABLE

NONE

ONE

TWO

THREE

10

11

12

13

14

15

C0234-05

FIGURE 1: FIK-BB-2 CABINET

FIK-IM-10 module positions so that all of the status indicators are visible. For 
cabinet dimensions refer to the FIK-BB-2 instruction manual.

INCLUDED:

(6) 1 x 4 Terminal 

Blocks

(2) 1

¼

" (32mm) 

Stand offs

(3) Shunts

(10) 47k Ohm End 
of Line Resistors

(2) Nuts

(4) Machine Screws

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

3.75 mA @ 24V

Alarm Current: 

55 mA (assumes all ten LEDs solid on)

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8" H x 5.8" W x 1.25" D 

Accessories: 

FIK-BB-2 Cabinet and Chassis

Wire Gauge: 

12-18 AWG

Maximum IDC

Wiring Resistance: 

1500 Ohms

Maximum IDC Voltage: 

10.2 VDC

Maximum IDC Current: 

240 µA (each circuit)

I56-6893-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

R

 704 SW 10th Street

 Blue Springs, MO 64015

 Phone: 816.229.3405; Fax: 816.228.9277 

www.fike.com

 

FIK-IM-10 

Ten Input Monitor Module

http://www.fike.com/06-912

For system/product documentation including 

installation, operation, and maintenance, 

scan QR code or enter URL provided. 

  

I56-6893-000 

 

 1/15/2021

Reviews: