BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE:
This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FIK-IM-10 Ten Input Monitor Module is intended for use in an intelligent
alarm system. Each monitor module is intended to interface between a control
panel and normally open contact devices, such as pull stations. A common
SLC input is used for all modules, and the initiating device loops share a
common supervisory supply and ground. Otherwise, each monitor operates
independently from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first mod-
ule from 01 to 150 (01 to 90 on panels that support up to 99 addresses).
The remaining modules are automatically assigned to the next nine higher
addresses. Provisions are included for disabling a maximum of two unused
modules to release the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the LEDs to blink,
latch on, or latch off.
C0202-00
SHIPPED ON BOARD:
(1) Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Fike system control panel.
COMPONENTS
The following is a description of the FIK-IM-10 mounting framework:
• One or two FIK-IM-10 modules can be installed in an FIK-BB-2 cabinet.
The FIK-BB-2 cabinet has a built-in chassis that will accommodate one or two
FIK-IM-10 modules.
The front FIK-IM-10 module positions of each chassis are offset below the rear
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
BASE
ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
BASE
ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
10
11
12
13
14
15
C0234-05
FIGURE 1: FIK-BB-2 CABINET
FIK-IM-10 module positions so that all of the status indicators are visible. For
cabinet dimensions refer to the FIK-BB-2 instruction manual.
INCLUDED:
(6) 1 x 4 Terminal
Blocks
(2) 1
¼
" (32mm)
Stand offs
(3) Shunts
(10) 47k Ohm End
of Line Resistors
(2) Nuts
(4) Machine Screws
SPECIFICATIONS
Normal Operating Voltage:
15-32 VDC
Stand-By Current:
3.75 mA @ 24V
Alarm Current:
55 mA (assumes all ten LEDs solid on)
Temperature Range:
32°F to 120°F (0°C to 49°C)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8" H x 5.8" W x 1.25" D
Accessories:
FIK-BB-2 Cabinet and Chassis
Wire Gauge:
12-18 AWG
Maximum IDC
Wiring Resistance:
1500 Ohms
Maximum IDC Voltage:
10.2 VDC
Maximum IDC Current:
240 µA (each circuit)
I56-6893-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
R
704 SW 10th Street
Blue Springs, MO 64015
Phone: 816.229.3405; Fax: 816.228.9277
www.fike.com
FIK-IM-10
Ten Input Monitor Module
http://www.fike.com/06-912
For system/product documentation including
installation, operation, and maintenance,
scan QR code or enter URL provided.
1
I56-6893-000
1/15/2021