BEFORE INSTALLING

If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 
Disconnect the power to the control panel before installing the modules. This 
system contains static sensitive components. Always ground yourself with a 
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably 
grounded.

NOTICE: This manual should be left with the owner/user of this equipment. 

GENERAL DESCRIPTION

The FIK-CR-6 Six Relay Control Module is intended for use in an intelligent 
alarm system. Each module is intended for Form-C switching applications, 
which do not require wiring supervision for the load circuit. A single isolated 
set of dry relay contacts is provided for each module, which is capable of 
being wired for either normally open or normally closed for each operation. 
Each module has its own address. A pair of rotary code switches is used to set 
the address of the first module from 01 to 94 (or 01 to 154 for panels that sup-
port 159 addresses). The remaining modules are automatically assigned to the 
next five higher addresses. Provisions are included for disabling a maximum 
of three unused modules to release the addresses to be used elsewhere. Each 
FIK-CR-6 module also has panel controlled green LED indicators. The panel 
can cause the LEDs to blink, latch on, or latch off.

CONTENTS INCLUDE:.

(6)  1 × 3 Terminal Blocks 
(1)  1 × 4 Terminal Blocks
(2)  1¼" (32mm) Stand offs
(4)  Machine Screws
(2) Nuts
(1)   Shunt (NOTE: For the disable position, not more than one shunt shall be 

installed at the same time)

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Fike series system control panel. 

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that 
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.

RELAY CONTACT RATINGS

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

2 A

25 VAC

PF = 0.35

Non-coded

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

0.46 A

30 VDC

(L/R = 20ms) 

Non-coded

0.7 A

70.7 VAC

PF = 0.35

Non-coded

0.9 A

125 VDC

Resistive

Non-coded

0.5 A

125 VAC

PF = 0.75

Non-coded

0.3 A

125 VAC

PF = 0.35

Non-coded

I56-6894-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC Stand-By Current:1.90 mA @ 24V

Alarm Current: 

32 mA (assumes all six relays have been switched once and all six LEDs solid on)

Temperature Range: 

32°F to 120°F (0°C to 49°C) 

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8" H × 5.8" W × 1.0" D 

Accessories: 

FIK-BB-2 cabinet and chassis

Wire Gauge: 

12-18 AWG

Relay Current: 

30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control

R

 704 SW 10th Street

 Blue Springs, MO 64015

 Phone: 816.229.3405; Fax: 816.228.9277 

www.fike.com

FIK-CR-6

Six Relay Control Module

http://www.fike.com/06-912

For system/product documentation including 

installation, operation, and maintenance, 

scan QR code or enter URL provided. 

  

I56-6894-000 

 