![Fike 203-0003 Installation And Maintenance Instructions Download Page 4](http://html1.mh-extra.com/html/fike/203-0003/203-0003_installation-and-maintenance-instructions_2288460004.webp)
26-0350 Issue 11
Technical Data
Dimensions:
Diameter
105mm
Depth
62mm
Operating temperature:
-10
o
C to +50
o
C
Voltage Range:
24 to 42V DC
LED Indication:
Normal
50ms on / 20s interval
Fault
0.1ms on / 5s interval
Fire
50ms on / 400ms interval
Flammability
UL94-V2
IP Rating
IP 21C
System Compatibility:
MPS - Sita200plus V2.00 onwards.
MP - Sita200plus V2.30 onwards.
Duonet and Quadnet V1 onwards.
PRODUCT DESCRIPTION
VOLUME LEVEL (dB)
Type
Product
Code
Name
Low
Medium
High
MP
203 0003
Multipoint Mk3 (25/11/09 Onwards)
-
-
-
MPS
203 0001
Multipoint with Sounder Mk3 (25/11/09 Onwards)
65+
83
88
LOOP CURRENT (mA)
Type
Product
Code
Name
Quiescent
SP0 - Off
Low
Medium
High
MP
203 0003
Multipoint Mk3 (25/11/09 Onwards)
0.12
0.96
-
-
-
MPS
203 0001
Multipoint with Sounder Mk3 (25/11/09 Onwards)
0.12
1.00
1.48
4.03
5.84
BATTERY CURRENT (mA)
Type
Product
Code
Name
Quiescent
SP0 - Off
Low
Medium
High
MP
203 0003
Multipoint Mk3 (25/11/09 Onwards)
0.12
2.00
-
-
-
MPS
203 0001
Multipoint with Sounder Mk3 (25/11/09 Onwards)
0.12
2.00
3.01
8.37
12.04
DLU RATING
Type
Product
Code
Name
SP0 - Off
Low
Medium
High
MP
203 0003
Multipoint Mk3 (25/11/09 Onwards)
1
-
-
-
MPS
203 0001
Multipoint with Sounder Mk3 (25/11/09 Onwards)
1
1.5
4.5
6
N.B.
All specified volume and current readings, unless otherwise stated are taken using sound pattern SP3.
Technical Support
Contact your supplier for technical support on this product.
Due to the complexity and inherent importance of a life risk type system training on this equipment is essential, and
commissioning should only be carried out by competent persons. Fike cannot guarantee the operation of any
equipment unless all documented instructions are complied with, without variation. This unit complies with the EMC
directive.
Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is
reserved. Whilst every care has been taken to ensure that the contents of this document are correct at time of
publication, Fike shall be under no liability whatsoever in respect of such contents. E&OE.