Fike 203-0003 Installation And Maintenance Instructions Download Page 1

 

26-0350 Issue 11 

 

 

 

 
 

 

General Description 

 

The Multipoint is a plug-in type smoke detector that utilises a photo-electric sensing 
chamber to make a measurement corresponding to smoke density. The device also 
incorporates a thermistor sensing circuit to allow for accurate heat measurement. These 
elements allow the device to be configured to a smoke, heat or combined setting. Digital 
communication technology to the control panel is implemented allowing for accurate data 
transfer at high transmission speeds. This device is only compatible with the Sita200plus, 
Duonet and Quadnet ranges of control panels and may also incorporate a sounder 
(ignore all references to sounders if your device has no sounder).  

 
Before Installation 

 

The detector must be installed in compliance with the control panel installation manual. The installation must also 
meet  the  requirements  of  any  local  authority.  For  maximum  performance  the  detector  should  be  installed  in 
compliance to BS5839 Pt1 : 2002 + A2 : 2008. 

 

Spacing 
 

Fike  recommends  spacing  detectors  in  accordance  with  BS5839  Pt1.  Due  to  the  effects  of  IR  and  possible 
magnetic interference, detectors should not be fitted any closer than 500mm (preferably 1000mm) to a light fitting or 
any  other  source  of  IR  or  EMI.  In  addition  to  this  recommendation  the  device  should  be  mounted  so  that  the 
indication  LED  is  facing  towards  the  light  source.  For  more  specific  information  regarding  detector  spacing, 
placement and special applications please refer to BS5839 Pt1 : 2002 + A2 : 2008. 

 

Detector Installation 
 

Fix the base in a suitable position using the two screw slots provided, remembering to allow enough cable length for 
termination. All wiring must be installed in compliance with the recommendations laid out by BS5839 Pt1 : 2002 as 
well  as  any  special  recommendations  documented  in  the  control  panel  installation  manual. 

The  cabling  used 

should be of a 2-core 1.5mm

2

 screened, fire resistant type, and is to be wired in the form of a screened 2-

core  loop returning to the control panel.  The use of spurs on this system is not permitted.

 Cables may be 

terminated  into  the  connectors  mounted  in  the  base,  as  shown  below.  Care  should  be  taken  when  terminating 
devices to ensure all cables are correctly sleeved and connections are secure. Improper connections will prevent a 
system from responding properly in the event of a fire. 
 

 

Terminal 

Description 

SCRN 

Screen 

0V 

Remote LED -ve 

AUX +ve 

Auxve 

AUX -ve 

Auxiliary 0V 

+ve Out 

Loop +ve OUT 

0V Out 

Loop -ve OUT 

0V In 

Loop -ve IN 

+ve In 

Loop +ve IN 

S +ve 

Not Used 

 
 
The  Loop  +ve  (positive)  IN  and  the  Loop  +ve  (positive)  OUT  connections  are  split  within  the  base.  For  cable 
continuity  readings  at  the  commissioning  stage  the  supplied  link  must  be  fitted.  Please  remember  that  all  high 
voltage  testing  must  be  carried  out  before  the  installation  of  the  electronics,  otherwise  the  electronics  will  be 
damaged.  Please  also  note  that  the  SCRN  terminal  should  only  be  connected  to  the  loop  screen  and  NOT  the 
building earth. 
 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 
 
 

203-0003 Sita Multipoint Detector and  
203-0001 Sita Multipoint Detector / Sounder 

 

AUX +ve 

OV 

SCRN 

+ve Out 

 

AUX -ve 

     0V Out 

 

     0V In 

+ve In 

  

S +ve 