5.3.
Server Side Connection Descriptions
The adapter used for the Profibus driver must be declared in the connections section.
Section Title
Connections
Column Title
Function
Legal Values
Adapter Adapter
Name
Prof_DP
Protocol
Specify protocol used
Profibus_DP
Profibus_DP_Baud
Specifies network baudrate
9600, 19200, 93.75K, 187.5K,
500K, 750K, 1.5M, 3M, 6M,
12M
Example
// Client Side Connections
Connections
Adapter,
Protocol,
Profibus_DP_Baud
Prof_DP,
Profibus_DP,
19200
5.4.
Server Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric
characters
Node_ID
Station ID of the Slave
0-125
Must be same as Value used for
System_Station_Address
Protocol
Specify protocol used
Profibus_DP
Adapter
Specify which adapter is
connected to the FieldServer
Prof_DP
Example
//
Client Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Adapter
PDP_01,
1,
Profibus_DP,
Prof_DP