FS-8700-19_Metasys_N2 Driver Manual
Page 44 of 51
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-2296
Toll_Free
: 888-509-1970
Input Output Config Parameters
Relative Item Signal Condition Read/Write Johnson Tag Description
B(5)
11111
B(6)
000 = Not used
011 = ON/OFF Output
100 = DAT Output Type
101 = PAT Output Type
B(8)
110 = Multistage ON/OFF Type
121
FP
R/W
OCO3
PAT/DAT Timing for Output Module #3
122
Byte
R/W
OCN4
Output #4 Configuration
B(1)
00001 Src of Module (Analog Items 1..31)
?.
B(5)
11111
B(6)
000 = Not used
011 = ON/OFF Output
B(8)
123
FP
R/W
OCO4
PAT Dead Band/Multistate Hysteresis #3
124
Byte
R/W
OCN5
Output #5 Configuration
B(1)
00001 Src of Module (Analog Items 1..31)
?.
B(5)
11111
B(6)
000 = Not used
011 = ON/OFF Output
100 = DAT Output Type
101 = PAT Output Type
110 = Multistage ON/OFF Type
B(8)
111 = Three Windings Control
125
FP
R/W
OCO5
PAT/DAT Timg Outpt Mod #5 FSB-pnt #1
126
Byte
R/W
OCN6
Output #6 Configuration
B(1)
00001 Src of Module (Analog Items 1..31)
?.
B(5)
11111
B(6)
000 = Not used
B(8)
127
FP
R/W
OCO6
PAT/DAT Timg Outpt Mod #5 FSB-pnt #2
128
Byte
R/W
OCN7
Output #7 Configuration
B(1)
00001 Src of Module (Analog Items 1..31)
?.
B(5)
11111
B(6)
000 = Not used
B(8)
129
FP
R/W
OCO7
Fan Speed Break-point #3
130
spare
131
Word
R/W
ALG
Configuration Index 1
132
Word
Write
XST
Diagnostic Status
W(1)
Read
Gain x 2 Jumper
W(2)
Read
Integral Action Zeroing Jumper
W(3)
Read
Zone 1 Jumper
W(4)
Read
Zone 2 Jumper
W(5)
Clear
DIAL
Dial Request Status
W(6)
Not used
W(8)
Read
Intelligent Command Module Com Failure
W(9)
Read
XTAI1
not valid
W(10)
Read
XTAI2
not valid
W(11)
Read
XTAI3
not valid
W(12)
Read
XTAI4
not valid
W(13)
Read
EEPROM not protected