Optimal start / stop module
Relative Item
Signal Condition Read/Write Johnson Tag Description
0
Byte
Write
OSOPT
Module options
1
Word
Write
OSZT@
Zone temperature connection
2
Word
Write
OSOT@
Outdoor temperature connection
3
Word
Write
OSSP@
Zone temperature setpoint connection
4
Word
Write
OSOB@
Off setpoint bias connection
5
Word
Write
OSDI@
Disable module connection
6
Word
Write
OSDA@
Disable adaptive action connection
7
Word
Write
OSTS@
Connection at time schedule output
8
Word
Write
OSNX@
Connection at next output
9
Word
Write
OSTIM@
Connection at time to next output
10
FP
Write
OSPURGE
Minimum cool / heat time (min)
11
FP
Write
OSMAXST
Maximum start up time (min)
12
FP
Write
OSMAXSO
Maximum shut down time (min)
13
FP
Write
OSBHK
Start mode building heating factor
14
FP
Write
OSBCK
Start mode building cooling factor
15
FP
Write
OSSBHK
Stop mode building heating factor
16
FP
Write
OSSBCK
Stop mode building cooling factor
17
FP
Write
OSFW
Percentage adaptive control (filter weight)
18
FP
Write
OSHTD
Outdoor heating design temperature
19
FP
Write
OSCTD
Outdoor cooling design temperature
20
FP
Write
OSCRNG
Control range
21
FP
Write
OSSP
Zone temperature on setpoint
22
FP
Write
OSOB
Zone temperature off setpoint
23
FP
Write
OSTIM
Remaining time to next event
24
Byte
Write
OSSTA
Operating status