FS-8700-97 Lutron Machine Manual
Page 23 of 24
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
5.3.15
Map Descriptor Example 11 - Analog Value (Zone and Area Machine)
A read from the Analog Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a system variable in the Lutron eLumen panel.
The variable values range from 0 to 255. The Lutron Machine Map Descriptors are regularly updated with system variable values from the active Binary Value Map
Descriptors. A write to the Analog Value Data Array will set the system variable to the written value.
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name
, Data_Type , Object_ID , Length , Relinquish_Default
SMD00_AV
, Analog_Value
, 0
, Passive
, Virtual_BCU_11 , AV
, 1
, 512
, 0
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function
, Node_Name , Grafik_Command , Sys_Var , Length
Zone_Vara_0
, Analog_Value
, 0
, Passive_Client , LUT_GRF6_0 , Sys_Var_Val
, 0
, 512
The Passive_Client function is used to prevent double-polling the Lutron eLumen panel for system variables. The Analog Value Map Descriptors should be set up identical
to the Binary Value Map Descriptors in terms of the Sys_Var and Length fields to ensure system variable values will be stored correctly.