FS-8700-97 Lutron Machine Manual
Page 15 of 24
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
Preloads
Data_Array_Name , Preload_Data_Format , Preload_Data_Value , Location
// Analog Output1 Object ID 1
Zone_pars_AO1
, Uint16
, 0
, 0
Zone_pars_AO1
, Uint16
, 1
, 1
// Analog Output1 Object ID 2
Zone_pars_AO1
, Uint16
, 2
, 2
Zone_pars_AO1
, Uint16
, 3
, 3
5.3.9
Map Descriptor Example 6 - Analog Output 2 (Zone and Area Machine)
A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts on the Lutron eLumen panel. The value
written into the Analog Output Data Array is used as an offset into the Data Array defined under “DA_Lut_List” to retrieve a script number. Script numbers range from 0
to 65535.
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name
, Data_Type , Object_ID , Length , Relinquish_Default
SMD512_AO
, Analog_Output
, 512
, Passive
, Virtual_BCU_11 , AO
, 513
, 512
, 0
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Grafik_Command , DA_Lut_List
, DA_Lut_List_Offset , Length , Multi_Scripts_Length
Run_script_512
, Analog_Output
, 512
, Awt
, LUT_GRF6_0 , Run_Script_Multi , Scr_Lst_AO2_512 , 0
, 1
, 10