4.2.
Client Side Connection Descriptors
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
1
Protocol
Specify protocol used
SNP
Baud*
Specify baud rate
110 – 19200, standard baud rates
only (Vendor limitation),
19200
Parity*
Specify parity
Even,
Odd
, None
,
Mark, Space
Data_Bits*
Specify data bits
7,
8
Stop_Bits*
Specify stop bits
1
Handshaking* Hnadshaking is not supported
None
Poll _Delay*
Time between internal polls
0-32000 seconds,
1 second
Timeout
The timeout specified for the connection is used as the data link layer
timeout. It is also used as the timeout for each Map Descriptor if a timeout
is not explicitly defined for a Map Descriptor.
Example
//
Client Side Connections
Connections
Port,
Protocol,
Baud,
Parity,
Handshaking,
Poll_Delay
P1,
SNP,
19200,
Odd,
None,
0.100s
GE Port Defaults
Series 90-30 PLC’s
Series 90-70 PLC’s
Baud
19,200
19,200
Data Bits
8
8
Parity
Odd
Odd
Stop Bits
1
1
Max Link Idle Time
10 Secs
5 Secs
GE Port Capabilities
Baud
300, 600, 1200, 2400, 4800, 9600, 19200
Data Bits
8
Parity
Odd, Even, None
Stop Bits
1, 2
Max Link Idle Time
1 to 60 Secs
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.