FS-8700-47 DNP 3.0 Driver Manual
Page 9 of 51
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
4.2.
Client Side Connection Descriptors
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected to the
FieldServer
P1-P8, R1-R2
1
Baud*
Specify baud rate
110 – 115200, standard
baud rates only
Parity*
Specify parity
Even, Odd,
None,
Mark,
Space
Data_Bits*
Specify data bits
7,
8
Stop_Bits*
Specify stop bits
1
Protocol
Specify protocol used
DNP
Handshaking* Specify hardware handshaking
None
Poll Delay*
Time between internal polls
0-32000 seconds,
1
second.
Application*
Versions of the driver prior to 1.02a used a different
method to calculate DA offset. Refer to Appendix A.16.
It is also possible to use this parameter to control if link
resets are used/required. Refer to Appendix A.15.
OriginalStyle,
NoLink,
OrigStyle-NoLink
Example
// Client Side Connections
Connections
Port
,Baud ,Parity ,Protocol ,Handshaking ,Poll_Delay
R1
,9600 ,None
,DNP
,None
,0.100s
4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up
to
32
alphanumeric
characters
Node_ID
DNP 3.0 station address of physical Server
node
0-65535
Protocol
Specify protocol used
DNP
Port
Specify which port the device is connected to
the FieldServer
P1-P8, R1-R21
Example
// Client Side Nodes
Nodes
Node_Name ,Node_ID ,Protocol ,Port
PLC 1
,1
,DNP
,P1
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.