Error Message
Explanation
DNP:#20 FYI. Node Indicates that
Event Buffers Have Overflowed.
This message is for information only. It is printed when a remote
device reports that its event buffers have overflowed.
DNP:#21 FYI. Length=%d invalid.
Setting to %d.
DNP:#23 FYI. Store rqsted but no
Data.
A poll for data contained a response with no data. This can be
valid, e.g. you request Change Data and there isn’t any.
DNP:#25 FYI. Slave Cant use
Qual=6. for Md=<%s>
You cannot use a qualifier of 6 when configuring a Server. See
Appendix A.11 for a list of valid qualifiers.
7
DNP:#27 Err. Slave: Too many
bytes=%s
to
send.
Reduce
message length
Change the Map Descriptor length so that the message contains
fewer data bytes.
7
DNP:#29 Err. Cant process this
qualifier (%d)
The driver does not support this qualifier when processing response
from a remote DNP device. Configure the device to use a different
qualifier.
7
DNP:#30 FYI. Data to store but
no mapDesc found.
A message has been received from a remote DNP device but the
driver has not been configured to store this data.
DNP:#31 Resp. data contained
obj=%d vari=%d. MD rqd for
storage.
Some responses (Class Data) contain multiple data types. The
driver could not find a Map Descriptor to store some of the data.
Refer to Section 4.4.7 to correct the problem.
7
DNP:#32 Err. Cant store for index
style %d
The driver can only store data from messages where the data
elements are indexed in a supported style. Take a log and send
with your configuration file to FST Tech Support.
DNP:#33 Err. Qty items + array
offset > end array. md=<%s>
Cant store all. qty/max= %d/%d
You need to make the data array longer (and/or the length of the
Map Descriptor.)
7
DNP:#35 Err. Relay
Output.
Status data array too short.
DNP:#36 Err. Relay Output.
Status data array too short.
The Data Array designated with e DA_Byte_Name parameter in the
CSV file is too short.
7
DNP:#37 Err. Relay Output.
Bridge cant implement action
code
The driver only supports ‘Latch On’ and ‘Latch Off’ and Relay
output actions. Reconfigure the remote device to use a different
relay action.
DNP:#38 Err. Storage Method
Unknown. (%d)
Take a log and send the log and configuration file to FST Tech
Support.
DNP:#40 Err. Abandoned data
store. Too many data object
types.
The DNP 3.0 driver can process a max of 20 different data objects
when storing class data. Reconfigure the remote device for fewer
data objects in the class requested.
DNP:#41 Err. MD=<dnp-ii> is too
short. Rqd=%d
DNP:#41 Err. MD=<dnp-stats> is
too short. Rqd=%d
8
DNP:#42 FYI. You could have
used a MD called <dnp-ii> to
expose diagnostic info.
DNP:#42 FYI. You could have
used a MD called <dnp-stats> to
expose diagnostic info.
Error! Reference source not found.
and 0 contain additional
information.
DNP:#43a Err. Diagnostic #3. Call
Support.
If any variation of MSG #43 is printed, take a log and call Tech
support.
DNP3:#44 FYI. Link Reset
Suppressed. Port=%d
The configuration file has suppressed the requirement for link reset.
If this corresponds to your expectation then you can safely ignore
this message, If not, see Appendix A.15
7
Edit the CSV file, download to the FieldServer and reset the FieldServer.