Appendix C.
Reference
EST3 Data Format:
Appendix C.1.1.
Input data format
Each input device is associated with a 16-bit value. The contents of the 16 bits are used to generate status types as shown in
the table below. Each incoming event is allocated to a status type depending on its device type as shown in the table. It is
possible to override this default status type allocation. Refer to 0 for more information.
Type
Encode Value Alarm Trouble Supervisory Monitor CO Active Others
Smoke
0
Y
Pull
1
Y
Heat
2
Y
Waterflow
3
Y
Stagetwo
4
Y
Zone
5
Y
AlarmVerify
6
Y
PreAlarm
7
Y
Security
8
Y
Station
9
Y
Emergency
10
Y
Supervisory
11
Y
Valve
12
Y
GateValve
13
Y
Tamper
14
Y
Temperature
15
Y
Power
16
Y
Signal
17
Y
TroubleOpen
18
Y
TroubleShort
19
Y
LocalTrouble
20
Y
MaintAlert
21
Y
DirtyHead
22
Y
DeviceComm
23
Y
GroundFault
24
Y
InternalTrouble
25
Y
BadType
26
Y
BadPersonality
27
Y
UnexpectedDevice
28
Y
CommonTrouble
29
Y
RelayConfirmation
30
Y
Monitor
31
Y
LocalMonitor
32
Y
Damper
33
Y
Fan
34
Y
Door
35
Y