FS-8700-16 BACnet PTP Serial Driver Manual
Page 8 of 32
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-9042
Toll Free
: (888) 509-1970
4.2
Setting the FieldServer Node_ID
Section Title
FieldServer
Column Title
Function
Legal Values
System_Node_ID Configure Node_ID of FieldServer 1-255
Example
// FieldServer
FieldServer
Title
, System_Node_ID
BACnet_PTP
, 11
4.3
Client Side Connection Descriptions
Section Title
Connections
Column Title Function
Legal Values
Port
Port Name
P1-P8
2
Baud*
Specify baud rate
110; 300; 600; 1200; 2400; 4800;
9600
; 19200; 38400; 57600; 115000
Parity*
Specify parity
Odd, Even,
None
Data_Bits*
Specify data bits
7,
8
Stop_Bits*
Specify stop bits
1
,2
Protocol
Specify Protocol Used BACnet_PTP
Example
// Client Side Connections
Connections
Port
, Baud , Parity , Data_Bits , Stop_Bits , Protocol
P8
, 9600 , Even
, 7
, 1
, BACnet_PTP
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.