6
CONFIGURING THE BACNET ROUTER
6.1
Settings
6.1.1
Button functions
Save - write the currently displayed settings to the device. A restart will be required to
apply the updated settings.
Reload - discard the currently displayed settings and reload the settings stored on the
device. This will undo any unsaved edits.
Defaults - discard the currently displayed settings and load default settings. This must
still be saved and the device must be restarted for the default settings to be applied.
Restart - restarts the device.
6.1.2
Network Settings
The IP settings for the Router are also used by both BACnet/IP
connections. The IP settings can be changed in the Network Settings
section as shown.
6.1.3
All connections
Network Number - set up the BACnet network number for the connection. Legal values are 1-65534. Each
network number must be unique across the entire BACnet internetwork.
Enable - enable or disable the connection; note that BACnet/IP Primary is always enabled.
6.1.4
BACnet IP Primary
Device Instance and Device Name - A BACnet Router must
provide a Device Object. Configure its name and Instance Number
here. Take care to select a Device Instance Number that is unique
across the entire BACnet internetwork.
IP Port - the BACnet/IP default is 47808 (0xBAC0), but a
different port number may be specified here.