Device Name
Enter a name for the Device. The name may not contain any commas.
Device Location
Enter a location for the Device. The location may not contain any commas.
MAC Address
Enter a value between 0 and 127 that is unique for this MS/TP segment.
Max_Master
Sets the highest allowable address for MS/TP master nodes on the network. Set a
value between 0 and 127.
Max_Info_Frames
The number of frames that can be sent by this device during a single token hold. Set a
value between 1 and 100.
Token Usage Timeout (ms) Set a larger value to improve network reliability with slow devices.