Offset Description
21
Stores the select code of the most recent select message sent by the Client
22
Stores the sub-device/port select code of the most recent sub-device/port select message sent by the
Client
23
Each time Client side sends a message this stat increments by 1
24
Each time Client side sends a message this stat increments by the number of bytes in the message
25
Increments by 1 each time a complete response is received from the field device
26
Increments by the number of bytes contained in a complete response received from the field device
27
Increments each time the device responds with‘#’ to indicate there is no current record.
Appendix B.3.
Sample and Hold Times
When this driver was field tested, using a 2100 and 4803, it was learned that the functions to read and write the
hold and samples did not work correctly. The devices ignored the messages. Even after working with HACH Tech
support these commands did not operate correctly. Therefore they should not be used until this issue is resolved.