Field Controls UV-AIRE UV-1500C Manual Download Page 7

page 7

WARNING:

 

Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness.

Never operate the UV-Aire

®

 Air Purifying System out of the plenum

. Avoid touching the glass portion of the lamp with your hands.

Replace the lamp by first guiding the end of the lamp through the hole on the left side of the UV chamber. 

6. 

Next, guide the other end of the lamp through the hole on the right side of the UV chamber. Hold the 

lamp in position while rotating the swivel bracket into position. Secure the lamp into position by tightening 

the wing nut onto the swivel bracket.

NOTE:

 UV lamps contain a small amount of mercury, like a typical fluorescent lamp. Check with your local 

waste management authority for local disposal or recycling requirements. According to the EPA’s Universal 

Waste Rule, these types of lamps may be disposed of into household waste.

Close the chamber access door and rotate the door clips to secure the door into position.

7. 

 
WARNING:

 Never expose eyes or skin to UVC light from any source. Looking 

directly at the UVC light may cause permanent eye damage or blindness. 

  

Plug the power cord back into the wall receptacle or restore power to the UV-

8. 

1500C circuit.

Turn the knob on the speed control to the on position, press the door switch in, 

9. 

and allow the motor to start and the lamp to light.  Wait 30 seconds.

Reset the lamp timer by using the eraser end of a pencil or the blunt end of a 

10. 

plastic ink pen and press and hold the timer-reset button on the circuit board 

for 30-45 seconds (See Figure 20).  After releasing the timer- reset button the 

LED on the front of the unit will flash twice indicating the timing circuit has been 

reset.  

Release the door switch, turn the knob on the speed control to the off position and close the front cover of 

11. 

the unit. Secure the cover with the door mounting screws.

Turn the speed control knob clockwise to turn on the unit and adjust the motor/fan speed control to the 

12. 

desired airflow. After the fan has started the LED light will show a continuous “GREEN” color indicating 

proper unit operation.

Figure 20

REPLACING AIR FILTERS

Loosen the two door-mounting screws on front cover of the UV-1500C. Open the cover to expose the 

1. 

filters and the air purification chamber. (See Figure 16)

Replace the 12” by 12” air filter by removing the filter and replacing the filter with the wire support side 

2. 

of the filter installed toward the fan intake of the unit. (See Figure 17)

Replace the carbon filter by removing the old filter and inserting the new filter back into the filter holder 

3. 

being sure safety switch is depressed.

TROUBLESHOOTING GUIDE

If the LED is illuminating a “YELLOW” color and the circuit board alarm beeps every 15 minutes, then  the 

1. 

lamp should be replaced soon.

If the LED is illuminating a “RED” color and the circuit board alarm beeps every 5 minutes, then the lamp 

2. 

should be replaced.

If lamp does not light up 1) be sure the safety switch located in the carbon filter chamber is depressed 

3. 

with pressure from the filter or 2) replace lamp.

If lamp still does not light up after checking the safety switch or replacing the lamp, replace ballast. 

4. 

Summary of Contents for UV-AIRE UV-1500C

Page 1: ...on Date Installed By Phone UV AIRE AIR PURIFYING SYSTEM Model UV 1500C ITEMS INCLUDED IN KIT 1 UV Aire UV 1500 unit 10 sheet metal mounting screws 2 drop ceiling cover plates 4 wall and drop ceiling mounting brackets 1 Ultra Violet lamp 1 instruction sheet 1 2x4 electrical conduit box and cover 4 intake air filters 1 carbon filter For best results operate the UV 1500 continuously 24 hours a day UV...

Page 2: ...afety shut off switch that disconnects power to the fan and the lamp if the front 2 access door is opened The UV 1500C is equipped with a circuit board to monitor the operation of the UV lamp it indicates the 3 operation of the lamp through an LED indicator light mounted on the front access door The circuit board indicates good operation of the lamp by a continuous GREEN color on the LED light Aft...

Page 3: ...our mounting brackets to allow the unit to be mounted onto a wall To install the mounting brackets remove the eight mounting screws from the back of the UV 1500C 1 See Figure 2 Install the four mounting brackets onto the back of the housing securing them with the mounting screws 2 you just removed See Figure 3 Determine the desired location on the wall a 120 volt wall receptacle should be within 5...

Page 4: ...oot ceiling tile space 23 3 4 Align the edges of the extension cover to the front of the UV 1500C body and use the holes in the cover as a template to mark the mounting hole locations on the UV 1500C body See Figure 6 Drill a 3 1 8 hole into the body of the UV 1500C at the marked locations See Figure 7 Secure the extension covers the UV 1500C body with the supplied metal screws See Figure 8 9 4 Re...

Page 5: ...auge wire or other 10 suspended ceiling support method between the installed ceiling anchors and the four mounting brackets on the back of the UV 1500C See Figure 14 Wire the UV 1500C in accordance with the National Electrical Code manufacturer s recommendations 11 and or applicable local codes UNIT MUST BE GROUNDED Check ground circuit to make certain that the unit has been properly grounded The ...

Page 6: ...oor to open See Figure 18 3 Unplug ballast plug from end of lamp and loosen the wing nut on swivel bracket Swing swivel bracket 4 away from the lamp See Figure 19 Remove lamp carefully by sliding the lamp to the left through the hole on the left side of the chamber 5 After exposing the connection end of the lamp inside the chamber remove the lamp through the front of the unit NOTE When replacing t...

Page 7: ...nd press and hold the timer reset button on the circuit board for 30 45 seconds See Figure 20 After releasing the timer reset button the LED on the front of the unit will flash twice indicating the timing circuit has been reset Release the door switch turn the knob on the speed control to the off position and close the front cover of 11 the unit Secure the cover with the door mounting screws Turn ...

Page 8: ...uality stickers Product serial number plates or electronic serial numbers have been removed altered or rendered illegible shall not be covered under the limited warranty 4 Defective Product must be returned to Company postage prepaid 5 IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY INDIRECT SPECIAL INCIDENTAL CONSEQUENTIAL OR SIMILAR DAMAGES INCLUDING BUT NOT LIMITED TO LOST PROFITS OR REVENUE INABIL...

Reviews: